After start-up of the SC200:
Press any key to silence the alarm.
Depending on the configuration file settings, the alarm LED(s) may be on and the SC200 will
display some system alarm messages. This is normal. For an explanation of alarm messages
see Alarm Descriptions in the System Controller Operation Handbook.
The LCD module shows the default screen. See details.
If no load or battery is connected the current will be 0A.
If fitted and enabled, the LVD(s) operate.
5
Check for correct operation of the rectifier(s). Check only the green Power On LED(s) are
on (no alarm LEDs).
Use the SC200 keypad to check that all rectifiers are registered. See details in the System
Controller Operation Handbook.
6
If any problems see Troubleshooting on page
. Otherwise switch on all remaining
rectifiers.
Task 4 - Configure the dc power system
The operational settings of the dc power system are stored in a configuration file loaded into the
SC200 system controller. Refer to the System Controller Operation Handbook for details (see
Related Information on page
The SC200 is supplied pre-loaded with a configuration file. If this configuration file has been
customized for the site then no further configuration changes will be necessary.
If the configuration file is not fully customized for the site then check the following settings and
change if necessary. It is important that these settings are correct before progressing further.