background image

 WARNING

THERE IS NO PROVISION FOR IN-SERVICE ADJUSTMENTS 

OF CONTACT WIPE AND STROKE. ALL SUCH ADJUSTMENTS 

ARE FACTORY SET AND SHOULD NOT BE ATTEMPTED IN 

THE FIELD.

Contact Erosion Indicator

Eaton’s VR-Series vacuum contacts are contained 

inside the interrupter, where they remain clean and 

require no maintenance. However, during high current 

interruptions there may be a minimal amount of erosion 

from the contact surfaces. If contact erosion reaches 

approximately 1/8 inch, the interrupter must be replaced. 

The purpose of the contact erosion indicator is to 

monitor the erosion of the vacuum interrupter contacts. 

A contact erosion indicator mark is located on the 

moving stem of the interrupter.

In order to determine if the contacts have eroded to the 

extent that the interrupter must be replaced, close the 

circuit breaker and observe the erosion mark placed on 

each vacuum interrupter moving stem from the rear of 

the circuit breaker. If the mark on the interrupter stem 

is visible, erosion has not reached maximum value thus 

indicating satisfactory contact surface of the interrupter. 

If the mark is no longer visible, the vacuum interrupter 

assembly must be replaced.

The erosion indicator is easily viewed from the rear on 

the 18WR or 29WR element designs. Because of the 

nature of the 5kV 20-WR element inverted design, the 

erosion indicator is not easily viewed, although it is 

possible with the use of a light and a dental type mirror.

Vacuum Bottle Contact Inspection

 WARNING

FAILURE TO REPLACE A VACUUM INTERRUPTER ASSEMBLY 

WHEN CONTACT EROSION MARK IS NOT VISIBLE OR WIPE 

IS UNSATISFACTORY, WILL CAUSE THE CIRCUIT BREAKER 

TO FAIL TO INTERRUPT AND THEREBY CAUSE PROPERTY 

DAMAGE OR PERSONNEL INJURY.

Contact Wipe and Stroke

Contact wipe is the indication of (1) the force holding the 

vacuum interrupter contacts closed and (2) the energy 

available to hammer the contacts open with sufficient 

speed for interruption.
Stroke is the gap between fixed and moving contacts of 

a vacuum interrupter with the circuit breaker open. 
The circuit breaker mechanism provides a fixed amount 

of motion to the operating rods. The first portion of the 

motion is used to close the contacts (i.e. stroke) and the 

remainder is used to further compress the preloaded 

wipe spring. This additional compression is called wipe. 

Wipe and stroke are thus related to each other. As the 

stroke increases due to the erosion of contacts, the 

wipe decreases. A great deal of effort and ingenuity has 

been spent in the design of VR-Series circuit breakers, in 

order to eliminate any need for field adjustment of wipe 

or stroke. 
The adequacy of contact wipe, as well as the overall 

system condition, can be determined by simply 

observing the vacuum interrupter side of the operating 

rod assembly on a closed circuit breaker. The visible 

“T” shape cutout on the loading spring is an indicator 

used to determine whether the loading springs are 

maintaining the proper contact pressure to keep the 

contacts closed. Severe contact erosion would result 

in an unacceptable implication from the “T” shape 

indicator. If the wipe is not adequate, the vacuum 

interrupter assembly (Pole Unit) must be replaced. Field 

adjustment of the vacuum interrupter assembly is not 

possible.

otee:

N

It may be necessary to use a small mirror and flashlight to 

clearly see the “T” shape indicator. The figure below shows the 

procedure for determining the contact wipe of each spring type. 

If any part of the Red or Gray

indicator is visible:

“Wipe” is Satisfactory.

If any part of the T-Shape Cutout  

indicator is visible:

“Wipe” is Satisfactory.

If any part of the Red or Gray indicator 

is NOT visible:

“Wipe” is Unsatisfactory.

If any part of the T-Shape Cutout  

indicator is NOT visible:

“Wipe” is Unsatisfactory.

Contact Wipe and Stroke: White Contact Springs

Contact Wipe and Stroke: Blue, Red, or Brown Contact Springs

otee:

N

Click the image below to view a satisfactory contact wipe and stroke.

7

EATON

   |   Visual Instruction Booklet Essentials   |   DST-2-VR - 18WR Element   |   May 2017  

Summary of Contents for DST-2-VR

Page 1: ...For VR Series Circuit Breakers This is a user interactive supplemental booklet This material is intended to enhance the technical information included in the instruction booklet for the vacuum replace...

Page 2: ...on and maintenance of medium voltage circuits and equipment should be permitted to work on these circuit breakers Always remove the circuit breaker from the enclosure before performing any maintenance...

Page 3: ...m Interrupter Assembly Each interrupter is assembled at the factory as a unit to assure correct dimensional relationships between working components The interrupter assembly consists of a vacuum inter...

Page 4: ...ENTIAL TESTS ARE NOT RECOMMENDED BY EATON DO NOT APPLY DC AT ANY LEVEL TO VR SERIES POWER CIRCUIT BREAKERS With the circuit breaker open and securely sitting on the floor connect all top front primary...

Page 5: ...L BELOW MAXIMUM PERMITTED BY STANDARDS HOWEVER AS A PRECAUTIONARY MEASURE AGAINST POSSIBILITY OF APPLICATION OF HIGHER THAN RECOMMENDED VOLTAGE AND OR BELOW NORMAL CONTACT SPACING IT IS RECOMMENDED TH...

Page 6: ...BOTTOM terminal of the phase being tested 8 Press the TEST button on the DLRO Once the TEST button is pressed 100A dc will flow through the phase being tested If the circuit breaker is not closed the...

Page 7: ...ent speed for interruption Stroke is the gap between fixed and moving contacts of a vacuum interrupter with the circuit breaker open The circuit breaker mechanism provides a fixed amount of motion to...

Page 8: ...d the motor eccentric These bearings are packed at the factory with a top grade slow oxidizing grease which normally should be effective for many years They should not be disturbed unless there is def...

Page 9: ...bracket and tighten Do not over tighten Fish wires through to terminal block Connect wires to terminal block TB1 and TB2 Install tie wraps to hold wire bundle Mechanically and electrically test the c...

Page 10: ...k the threads Remove the two screws on the right hand motor support plate using a 9 64in Allen wrench Remove the motor plate from the side sheet for the 5kV circuit breaker Remove the motor Verify the...

Page 11: ...afety Precautions Read and understand the instruction manual for specific instructions before attempting any maintenance repair or testing on the circuit breaker The user is cautioned to observe all r...

Page 12: ...VR Series Circuit Breaker DST 2 5 VR 350 2000A 12 EATON Visual Instruction Booklet Essentials DST 2 VR 18WR Element May 2017...

Page 13: ...VR Series Circuit Breaker DST 2 15 VR 1200A 13 EATON Visual Instruction Booklet Essentials DST 2 VR 18WR Element May 2017...

Page 14: ...nts and engineering services Eaton is positioned through its global solutions to answer today s most critical electrical power management challenges Eaton is a power management company with 2015 sales...

Reviews: