CloSure™ Test

Introductione:

 The CloSure™ Test is a simple yet 

extremely effective means to determine and monitor 

the ability of the mechanism to close the circuit breaker 

contacts fully. It provides a quantitative measure of the 

extra energy available in terms of over travel in inches 

to close the circuit breaker contacts to their full extent. 

It may be used periodically to monitor the health of the 

mechanism.
At times, circuit breakers are called upon to operate 

MOC (Mechanism Operated Control) switches that 

place extra load upon the closing mechanism of the 

circuit breaker. If this load is excessive, it can prevent 

the circuit breaker from closing fully. In such a case, it is 

important to determine that the circuit breaker will close 

fully. The CloSure™ Test provides this assurance.

General Informatione: 

If the CloSure™ travel obtained 

is as specified, the mechanism performance is 

satisfactory. If the CloSure™ travel does not conform as 

shown in the demonstration, contact Eaton for further 

information.

 WARNING

DO NOT ATTEMPT TO INSTALL OR PERFORM 

MAINTENANCE OR TESTS ON THE EQUIPMENT WHILE 

IT IS ENERGIZED. NEVER PUT YOUR HANDS NEAR THE 

MECHANISM WHEN THE CIRCUIT BREAKER IS IN THE 

CHARGED OR CLOSED POSITION. DEATH OR SEVERE 

PERSONAL INJURY CAN RESULT FROM CONTACT WITH 

ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO 

VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE 

TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED 

SAFETY PROCEDURES.

Safety Precautionse:

 Read and understand the 

instruction manual for specific instructions before 

attempting any maintenance, repair or testing on the 

circuit breaker. The user is cautioned to observe all 

recommendations, warnings and cautions relating to the 

safety of personnel and equipment.
The recommendations and information contained herein 

are based on experience and judgment, but should 

not be considered to be all-inclusive or covering every 

application or circumstance which may arise. If further 

information is required, you should consult an Eaton 

Electrical Services and Systems representative.

Testing Procedurese:

 Assuming that the circuit breaker 

is safely removed from the switchgear enclosure and 

positioned in an area outside the arc fault boundary, 

follow this procedure to perform the CloSure™ test. For 

further instructions on removal of the circuit breaker 

from the switchgear, refer to the appropriate section of 

the instruction manual.

Table 5. CloSure™ Tool Mounting / Testing Hole Locations

Circuit breaker 

LINE

APPROXIMATE

MECHANISM

CABINET 

WIDTH (INCH)

UPPER

MOUNTING 

HOLE

LOWER

MOUNTING

HOLE

MARKER

PLACEMENT

HOLE

18WR

20WR

29WR

18

20

27

A1

A1

A1

B2

B2

B2

C1

C2

C5

CloSure™ Tool Showing Mounting / Testing Hole 

Locations (6352C49H01) 

Illustrative Testing Tape  Sample

 (Illustration not to scale)

A-1

A-2

A-3
A-4

B-1

B-2

C-2

C-3

C-4

C-5

C-6

C-1

"X" Inches

Date     /     # of Breaker Operations     /     CloSure    Distance

TM

CloSure   Distance

TM

* Note:  

Use the center of the marker diameter to determine "X" distance

8.0

” to  

10

5

 

3/16"

  Approx

otee:

N

18WR element shown.

11

EATON

   |   Visual Instruction Booklet Essentials   |   DST-2-VR - 18WR Element   |   May 2017  

Summary of Contents for DST-2-VR

Page 1: ...For VR Series Circuit Breakers This is a user interactive supplemental booklet This material is intended to enhance the technical information included in the instruction booklet for the vacuum replace...

Page 2: ...on and maintenance of medium voltage circuits and equipment should be permitted to work on these circuit breakers Always remove the circuit breaker from the enclosure before performing any maintenance...

Page 3: ...m Interrupter Assembly Each interrupter is assembled at the factory as a unit to assure correct dimensional relationships between working components The interrupter assembly consists of a vacuum inter...

Page 4: ...ENTIAL TESTS ARE NOT RECOMMENDED BY EATON DO NOT APPLY DC AT ANY LEVEL TO VR SERIES POWER CIRCUIT BREAKERS With the circuit breaker open and securely sitting on the floor connect all top front primary...

Page 5: ...L BELOW MAXIMUM PERMITTED BY STANDARDS HOWEVER AS A PRECAUTIONARY MEASURE AGAINST POSSIBILITY OF APPLICATION OF HIGHER THAN RECOMMENDED VOLTAGE AND OR BELOW NORMAL CONTACT SPACING IT IS RECOMMENDED TH...

Page 6: ...BOTTOM terminal of the phase being tested 8 Press the TEST button on the DLRO Once the TEST button is pressed 100A dc will flow through the phase being tested If the circuit breaker is not closed the...

Page 7: ...ent speed for interruption Stroke is the gap between fixed and moving contacts of a vacuum interrupter with the circuit breaker open The circuit breaker mechanism provides a fixed amount of motion to...

Page 8: ...d the motor eccentric These bearings are packed at the factory with a top grade slow oxidizing grease which normally should be effective for many years They should not be disturbed unless there is def...

Page 9: ...bracket and tighten Do not over tighten Fish wires through to terminal block Connect wires to terminal block TB1 and TB2 Install tie wraps to hold wire bundle Mechanically and electrically test the c...

Page 10: ...k the threads Remove the two screws on the right hand motor support plate using a 9 64in Allen wrench Remove the motor plate from the side sheet for the 5kV circuit breaker Remove the motor Verify the...

Page 11: ...afety Precautions Read and understand the instruction manual for specific instructions before attempting any maintenance repair or testing on the circuit breaker The user is cautioned to observe all r...

Page 12: ...VR Series Circuit Breaker DST 2 5 VR 350 2000A 12 EATON Visual Instruction Booklet Essentials DST 2 VR 18WR Element May 2017...

Page 13: ...VR Series Circuit Breaker DST 2 15 VR 1200A 13 EATON Visual Instruction Booklet Essentials DST 2 VR 18WR Element May 2017...

Page 14: ...nts and engineering services Eaton is positioned through its global solutions to answer today s most critical electrical power management challenges Eaton is a power management company with 2015 sales...

Reviews: