3 Installation
3.3 Flush mounting in control panel
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
69
3.3.2 Mounting instructions (BG 1 and BG 2)
3.3.2.1 Free surrounding areas
→
An installation clearance of 25 mm must be maintained in front
of size 1 and size 2 (up to 32 A) DS7 soft starters. A top and
bottom clearance of 75 mm each is required. If the clearances
are smaller, derating will be necessary or it will be necessary to
use the optional DS7-FAN-032 fan.
All sizes can be mounted directly next to each other.
Side clearance is not required to other devices that do not
themselves require clearance at the sides.
Figure 50: Installation clearances for devices up to 32 A
Top: Devices without SmartWire-DT; bottom: Devices with
SmartWire-DT
→
If the point if installation is subject to continuous vibration or
shocks, design measures must be taken for dampening, such as
through the use of vibration dampers.
≧
25 mm
(≧ 0.98")
≧ 0
≧ 0
≧
75 mm
(≧
2.95")
≧
75 mm
(≧
2.95")
≧
25 mm
(≧ 0.98")