8 SmartWire-DT
8.9 Programming
202
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
8.9.7 Data types
There are special data types defined for PROFIdrive communications:
PROFIdrive-specific and standard data types.
8.9.7.1 PROFIdrive specific
TimeDifference (13
dec
)
The value used by the DS7-SWD soft starter for TimeDifference is stored in
the Sampling Time (PNU 962) parameter.
Example:
100 ms = 4971
dec
= 136B
hex
86400000 ms (= 1 day) = 4294967295
dec
= FFFFFFFF
hex
Normalised value: N2
N2 is a normalized value for relative scaling. N2 falls within a range of -200 %
to +200 %.
Conversion examples:
Without a sign bit:
0
dec
= 0x0000
hex
≙
0 %
1
dec
= 0x0001
hex
≙
0.0061 %
16384
dec
= 0x4000
hex
≙
100 %
32767
dec
= 0x7FFF
hex
≙
199.99 %
With a sign bit (bit 15):
-1
dec
= 0xFFF
hex
≙
-0.0061 %
-16384
dec
= 0xC000
hex
≙
-100 %
-32768
dec
= 0x8000
hex
≙
-200 %
For coding, the most significant bit (MSB) comes directly after the SN bit
(sign bit) in the first octet.
•
SN = 0: Positive numbers, including zero
•
SN = 1: Negative numbers
Data type
Code
(dec)
Code
(hex)
Bytes
Value range
Resolution
TimeDifference
13
D
2
0
≦
i
≦
4294967295
2
-31
≙
0.021 ms
Data type
Code
(dec)
Code
(hex)
Bytes
Value range
Resolution
N2 Normalized
value (16 Bit)
113
71
2
-200 %
≦
i
≦
(200 - 2
-14
) %
2
-14
≙
0.0061 %
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...