4 Operation
4.4 Potentiometer settings
98
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
4.4 Potentiometer settings
The soft starters can be adjusted as necessary for the application at hand by
using the three potentiometers, which are labeled
U-Start
,
t-Start
, and
t-Stop
respectively. Aside from these potentiometer settings, no additional
settings or prompts are required in order to run the soft starters.
When using DS7-SWD soft starters, these potentiometer settings can be
adjusted by means of parameters.
Figure 70: Potentiometer layout
Table 17: Potentiometer settings in the default settings
4.4.1 How the potentiometers work
Figure 71: Time-based control of motor voltage with a soft starter
→
section 8.9, “Programming” explains how to configure the
DS7-SWD soft starter’s parameters.
Potentiometer
Value
Function
DS
PNU
Index
DS
U-Start
30 - 100 %
Start voltage at which the ramp
function is started
30 %
11
4915
t-Start
1 - 30 s
Time in which the voltage is increased
from the value U-Start to 100 % with a
linear time ramp
5 s
111
50
t-Stop
0 - 30 s
Time in which the voltage is reduced
from 100 % to the value U-Start with a
linear time ramp
0 s
114
0
30
1
30
0
t-Start (s)
U-Start (%)
t-Stop (s)
20
10
20
10
100
30
U-Start
U
t-Start
t-Stop
t
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...