EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Activate on Evacuate
Fig 32
This feature allows the user to further filter what is required to operate when Evacuate is not locked.
Intermittent Fault Search
When a device goes into fault the panel has polled the detector a number of times to confirm the fault
(this is called integration), this can take up to 90 secs dependent on the length of the loop and number
of devices installed.
This feature forces the panel to indicate a fault on the first poll, which means the fault will appear
almost immediately.
This is particularly useful if a detector has an intermittent fault that would normally not be seen during
the standard polling sequence.
Generally, this setting should be initiated at the commissioning stage.
Logos
This menu allows the engineer to change the Logo shown on the front screen of the panel
Customers can also download their own logo into the panel from the Commissioning menu
The logo must be configured as a Monochrome Bitmap (.BMP) 160 x 80 pixels.