EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Sounder Tone
Recent product introductions include an Australian Bell Tone electronic sounder for school
applications. These operate as normal electronic sounders during an alarm situation but go to bell
tone when class change is operated.
This feature is at odds with the HMO settings above, so the panel must be informed if these sounders
are installed. Once installed within this menu HMO cannot be set.
FRE Double Knock Override
If FRE double knock is required in the panel programming, certain devices can be chosen to
automatically override this setting if triggered.
Options within this menu include Optical, Opto/thermal, Heat detector, Callpoint and I/O unit.
Change Text.
Fig 13
Zone/device text can be modified directly at the panel, once the change text option has been selected
and either address, zone or panel text has been selected a list of the available zones/devices is
displayed on the panel. A qwerty keyboard is the displayed on the screen and with the existing text
above, typing on the keyboard then changes the text.
The address and zone text is limited to 25 characters which is the maximum that can be transmitted
over the network. Both are also restricted in the Site Installer program.
Summary of Contents for DF6200
Page 1: ...DF6000 Applications Guide Including CF3000 FX6000 CF11 1200 DF61 6200 Annex 1 CF2000...
Page 29: ...29 Amended April 22 EMEA Fire Technical Support DF6000 CF3000 Applications Guide Fig 16...
Page 81: ...81 Amended Sept 21 Fig 73 Fig 74...
Page 84: ...84 Amended Sept 21 Fig 79...
Page 94: ...94 Amended Sept 21 Return to beginning of document End of Document...