background image

Effective 11/97

I.B. 48006

Cutler-Hammer

Instructions for Mechanical-Latch Attachments for Type
SJA, SJD, SJO and SJS Contactors, 360 or 720 Amperes

DANGER

HAZARDOUS VOLTAGE.

READ AND UNDERSTAND THIS MANUAL AND THAT
PERTAINING TO ITS ELECTRICALLY-HELD
CONTACTOR (SEE TABLE I) IN THEIR ENTIRETY
BEFORE INSTALLING OR OPERATING THE CON-
TROLLER.  INSTALLATION, ADJUSTMENT, REPAIR
AND MAINTENANCE OF THIS TYPE OF EQUIPMENT
MUST BE PERFORMED BY QUALIFIED PERSONNEL.
A QUALIFIED PERSON IS ONE WHO IS FAMILIAR
WITH THE CONSTRUCTION AND OPERATION OF
THIS EQUIPMENT AND THE HAZARDS INVOLVED.

APPLICATION

These instructions apply to Type SJA, SJD, SJO and SJS
contactors that are fitted with mechanical-latch attach-
ments.

Fig. 1  Type SJO with Latch Attachment

CAUTION

A LATCHED CONTACTOR SHOULD BE APPLIED
ONLY WHEN  NECESSARY,  AND WITH  DUE  RE-
GARD TO THE POSSIBLE FAILURE MODES OF
THE SYSTEM, FOR EXAMPLE, A POWER LOSS
OR SOLENOID COIL FAILURE.  ONCE LATCHED,
THE CONTACTOR WILL REMAIN CLOSED, AL-
LOWING A FAILURE.  SINCE POWER IS RE-
QUIRED TO TRIP THE  UNLATCH  SOLENOIDS,
PROVISION SHOULD BE MADE FOR MANUAL
TRIPPING,  USING THE  MECHANICAL TRIP  ARM,
OR A STANDBY POWER SUPPLY, SHOULD THE
MAIN CONTROL POWER BE LOST.

OPERATION

When a Type SJ contactor with latch attachment is open,
the latch mechanism is unlatched and de-energized.
When the coil of a latch contactor is momentaily ener-
gized, its armature closes, closing the main power

TABLE I.  REFERENCE MATERIAL

Electrically-Held

Ampere

Instruction

Contactor Type

Rating

I.L. or I.B.

Type SJA

360A

I.B. 48002

Type SJA

720A

I.B. 48005

Type SJD

360A

I.B. 48004

Type SJO

360A

I.L. 16-200-33

Type SJO

720A

I.L. 17047

Type SJS

360A

I.B. 48003

contacts.  As the armature seals to the magnet, a spring
pushes the latch arm up into position behind the arma-
ture to hold it closed mechanically, at the same time an
auxiliary coil-clearing contact (L63) on the contactor
opens the contactor coil circuit to de-energize the
contactor magnet.  Although the magnet is de-energized,
the contactor will remain latched closed until a trip coil is
energized or the latch is tripped mechanically by a push
against its trip arm.

Summary of Contents for Cutler-Hammer SJA

Page 1: ...AIN CLOSED AL LOWING A FAILURE SINCE POWER IS RE QUIRED TO TRIP THE UNLATCH SOLENOIDS PROVISION SHOULD BE MADE FOR MANUAL TRIPPING USING THE MECHANICAL TRIP ARM OR A STANDBY POWER SUPPLY SHOULD THE MA...

Page 2: ...ating See Table II for inrush VA requirements Some latch attachments are supplied with two trip solenoids each rated for a different voltage The latch attachment will unlatch when either solenoid is e...

Page 3: ...GARD DOOR TRIP TARGET FOR LATCH 30 TRAVEL REQ D TO TRIP 7 62 mm 4 30 109 2 mm 14 2 360 7 mm 10 20 259 1 mm 8 00 203 2 mm 2 75 69 9 mm 9 00 228 6 mm LATCH TRIP TARGET 8 07 205 0 mm 8 50 215 9 mm 2 75 6...

Page 4: ...ard the magnet and latch edge F travels across the cam roller easily As latch edge E passes the centerline of the cam roller the roller starts moving upward driven by the latch spring By the time the...

Page 5: ...ICAL Refer to the instruction material relating to the electri cally held version of the contactor See Table I Make sure all power circuits are isolated The contactor can be checked in its enclosure o...

Page 6: ...n cord as described previ ously under CHECK OUT MECHANICAL Remove the latch spring Block the single or bottom if there are two solenoid open temporarily with a pencil or other shim on top of its magne...

Page 7: ...solenoid armature of 120 to 130 inch 3 05 3 30 mm when the contactor is latched If there is no gap the sole noid armatures cannot move to push the latch arm d Increase the sensitivity of the latch by...

Page 8: ...Cutler Hammer 221 Heywood Road Arden NC 28704 TABLE III REPLACEMENT SOLENOIDS Trip Coil Rating Trip Solenoid Part No 115 120 VAC 48 VDC 5259C46H01 230 240 VAC 96 125 VDC 5259C46H02 460 480 VAC 230 VD...

Reviews: