background image

3

Installation manual 10679

Effective October 2017

BSPA Type 1 and Type 2 surge protective devices

Eaton.com/bussmannseries

3. Safety precautions

WARNING – SHOCK HAZARD – DO NOT OPEN
AVERTISSEMENT – RISQUE DE CHOC – NE PAS OUVRIR
WARNING NO SERVICEABLE PARTS
ATTENTION: AUCUNE PIÈCE REMPLACABLE OU RÉPARABLE.
A LICENSED/QUALIFIED ELECTRICIAN MUST COMPLETE ALL 

INSTRUCTIONS IN THIS MANUAL IN ACCORDANCE WITH THE 

NATIONAL ELECTRICAL CODE (NEC

®

), CANADIAN ELECTRICAL 

CODE (CEC), STATE, AND LOCAL CODES, OR OTHER 

APPLICABLE COUNTRY CODES. ALL APPLICABLE LOCAL 

ELECTRICAL CODES SUPERSEDE THESE INSTRUCTIONS.
CHECK THE VOLTAGE-RATING LABEL LOCATED ON THE SIDE 

OF THE BSPA TO VERIFY THAT THE ELECTRICAL SYSTEM’S 

VOLTAGE AND WIRING CONFIGURATION ARE THE SAME AS 

THE BSPA.
CONDUCTING DIELECTRIC, MEGGAR, OR HI-POTENTIAL 

TESTING WITH THE SPD INSTALLED WILL CAUSE INTERNAL 

DAMAGE TO THE SPD. THE SPD WILL CAUSE THE TEST TO 

FAIL.
IMPROPER INSTALLATION COULD CAUSE DEATH, INJURY 

AND EQUIPMENT DAMAGE. FOLLOW ALL WARNINGS AND 

CAUTIONS. COMPLETELY READ AND UNDERSTAND THE 

INFORMATION IN THIS INSTALLATION MANUAL BEFORE 

ATTEMPTING TO INSTALL OR OPERATE THIS EQUIPMENT.
ARC FLASH DURING INSTALLATION COULD CAUSE INJURY 

OR DEATH. USE APPROPRIATE SAFETY PRECAUTIONS AND 

EQUIPMENT FOR ARC FLASH PROTECTION.
INSTALLING A PROTECTION DEVICE WHICH IS UNDER RATED 

FOR THE ELECTRICAL SYSTEM VOLTAGE CAN CREATE A 

POTENTIALLY HAZARDOUS CONDITION.
CHECK THE FACILITY’S GROUNDING SYSTEM. ALL 

GROUNDING, BONDING AND EARTHING PRACTICES MUST 

MEET NEC, CEC AND LOCAL APPROVED PRACTICES. A POOR 

GROUND, OR A GROUNDING / BONDING VIOLATION WILL 

SERIOUSLY AFFECT THE SPD’S ABILITY TO FUNCTION AS 

SPECIFIED

4. BSPA catalog number

Each Bussmann series BSPA unit is identified by a catalog number 

(see example below). The catalog number identifies the unit’s 

specifications and permits specifying any combination to meet 

requirements.

 

BSPA  200  208Y  8  P

BSPA = Product family
Surge rating per phase
Voltage/system code
Options
NEMA enclosure

For example, BSPA unit catalog number 

BSPA200208Y8P

, where:

 BSPA

  = BSPA series

 200

  = peak surge current rating (50 kA – 200 kA)

 208Y

  = voltage code and system configuration

 8

  = feature option (1 – 8)

 P

  = enclosure type (NEMA 4X)

See section 

12. Catalog numbering system

 for additional surge 

current kA ratings, voltage codes and feature options.

5. BSPA product nameplate

Each BSPA unit has a nameplate affixed to its side that identifies the 

catalog number and specifications. The catalog number consists of 

letters and numbers that identify the BSPA unit’s kA rating, voltage 

code, feature option and enclosure type as shown in Figure 1.

Figure 1. BSPA product nameplate.

6 Installation

WARNING

A LICENSED/QUALIFIED ELECTRICIAN MUST COMPLETE ALL 

INSTRUCTIONS IN THIS MANUAL IN ACCORDANCE WITH THE 

NATIONAL ELECTRICAL CODE (NEC), CANADIAN ELECTRICAL 

CODE (CEC), STATE, AND LOCAL CODES, OR OTHER 

APPLICABLE COUNTRY CODES. ALL APPLICABLE LOCAL 

ELECTRICAL CODES SUPERSEDE THESE INSTRUCTIONS.
INSTALLING AN SPD THAT IS IMPROPERLY RATED FOR 

THE ELECTRICAL SYSTEM VOLTAGE COULD CREATE A 

POTENTIALLY HAZARDOUS CONDITION, RESULTING IN 

INJURY OR EQUIPMENT DAMAGE.
CHECK THE VOLTAGE-RATING LABEL LOCATED ON THE SIDE 

OF THE SPD TO VERIFY THAT THE ELECTRICAL SYSTEM’S 

VOLTAGE AND WIRING CONFIGURATION ARE THE SAME AS 

THE SPD.
TO PROVIDE THE BEST PROTECTION FOR SENSITIVE 

ELECTRICAL EQUIPMENT THE 10 AWG WIRES SHOULD BE 

LESS THAN 14” IN LENGTH, TWISTED TOGETHER AND THEN 

BOUNDED.
AVOID USING 90° CONDUIT ELBOWS AND KEEP THE CONDUIT 

RUN AS SHORT AND STRAIGHT AS POSSIBLE. SEE FIGURES 2 

AND 3.
WHEN MOUNTING THE SPD OUTDOORS, USE 

WEATHERPROOF CONDUIT AND FITTINGS TO MAINTAIN THE 

ENCLOSURE’S NEMA TYPE 4X RATING.
FOR USE ON CIRCUITS DELIVERING UP TO 5000 RMS AMPS. 

CONVIENT Á DES CIRCUITS PRODUCISANT AU PLUS 5000 A 

EFF.

Summary of Contents for BUSSMAN Series

Page 1: ...MOV while supporting power frequency voltage The Type 2 BSPA models equipped with EMI filtering are designed to protect sensitive equipment from electrical noise Proper installation is critical to ensure the BSPA unit operates as intended The Type 1 BSPA units are intended for installation between the secondary of the service transformer and the lineside of the service equipment overcurrent protec...

Page 2: ... accordance with established safety practices d is trained to render first aid e has received safety training to recognize and avoid the hazards involved f has the skills and knowledge pertaining to the construction and operation of this equipment and its installation IMPORTANT These procedures do not claim to cover all possible details or variations encountered with the installation of a Surge Pr...

Page 3: ...identifies the unit s specifications and permits specifying any combination to meet requirements BSPA 200 208Y 8 P BSPA Product family Surge rating per phase Voltage system code Options NEMA enclosure For example BSPA unit catalog number BSPA200208Y8P where BSPA BSPA series 200 peak surge current rating 50 kA 200 kA 208Y voltage code and system configuration 8 feature option 1 8 P enclosure type N...

Page 4: ...S POSSIBLE SEE FIGURE 3 6 2 Panel mounted The preferred mounting of the BSPA is directly to the electrical panel with its integrated male connector hub and the supplied 3 4 trade size conduit locknut Insert the wires through the panel wall being careful not to damage the wire insulation Install the provided locknut and tighten to 20 3 lb in 2 3 N m If the installation requires the NEMA 4X rating i...

Page 5: ...ncluded 3 4 14 NPS external thread Locknut Mounting feet included 36 inch long wires 3 75 95 3 2 38 60 4 8 48 215 4 10 25 260 4 11 50 292 1 7 48 190 0 9 25 235 0 10 50 266 7 4X Ø 0 223 0 80 20 3 6 67 169 4 0 0747 THK 1 51 38 4 1 51 38 4 6 4 Enclosure mounting feet and dimensions The mounting feet attach to the bottom of the enclosure with the provided screws hardware to mount the feet to wall are ...

Page 6: ...C typically requiring a 1 pole for single phase systems 2 pole for split phase systems or 3 pole for 3 phase systems 30 A branch circuit breaker to protect BSPA conductors Twist and bind the wires of the BSPA unit tightly together To optimize BSPA performance minimize overall lead length To maximize performance for wire lengths longer than four inches phase wires should be twisted once for each fo...

Page 7: ... product distributor or Bussmann series product representative as the SPD may be damaged 8 3 Options audible alarm and Form C relay Note Using Form C contacts is optional Connection is not required for the proper BSPA operation The audible alarm and Form C relay are tied to the phase LEDs on the BSPA enclosure If protection to one or more phases is lost the following will occur Single split and 3 ...

Page 8: ...utlined in appropriate Bussmann Division selling policies or other contractual agreements between the parties This manual is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and the Bussmann Division NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FI...

Page 9: ...re to give any advice or recommendations by the Bussmann Division shall not constitute any warranty by or impose any liability upon the Bussmann Division AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY FITNESS FOR PURPOSE SOLD PRODUCTIVENESS OR ANY OTHER MATTER In no event shall the Bussmann Division be liable for special or consequential dam...

Page 10: ...t of Eaton CSA is a registered trademark of the Canadian Standards Group NEC is a registered trademark of the National Fire Protection Association UL is a registered trademark of the Underwriters Laboratories Inc Eaton 1000 Eaton Boulevard Cleveland OH 44122 Eaton com Bussmann Division 114 Old State Road Ellisville MO 63021 United States Eaton com bussmannseries 2017 Eaton All Rights Reserved Prin...