2

Installation manual 10679

Effective October 2017

BSPA Type 1 and Type 2 surge protective devices

Eaton.com/bussmannseries

HAZARD OF ELECTRIC SHOCK, 

EXPLOSION OR ARC FLASH
WILL RESULT IN DEATH OR SERIOUS 

INJURY

Working on or near energized circuits poses 

a serious risk of electric shock. De-energize 

all circuits before installing or servicing this 

equipment and follow all prescribed safety 

procedures.

ELECTRIC SHOCK HAZARD

Ungrounded power systems are inherently 

unstable and can produce excessively high 

line-to-ground voltages during certain fault 

conditions.
During these fault conditions any electrical 

equipment, including an SPD, may be 

subjected to voltages, which exceed their 

designed ratings.
This information is being provided to the user 

so that an informed decision can be made 

before installing any electrical equipment on 

an ungrounded power system.

2. Signal words

The signal words “

DANGER

,” “

WARNING

,” “

CAUTION

” and 

NOTICE

” (along with their assigned symbol) throughout this 

manual indicate the degree of hazard the user may encounter.
These symbols and words are defined as:

DANGER

: Indicates a hazardous 

situation which, if not avoided, will 

result in death or serious injury.

WARNING

: Indicates a hazardous 

situation which, if not avoided, could 

result in death or serious injury.

CAUTION

: Indicates a hazardous 

situation which, if not avoided, could 

result in minor or moderate injury.

NOTICE

: Indicates a hazardous 

situation which, if not avoided, could 

result in property damage.

1.6 Qualified person

For the purpose of this instruction manual, a qualified person:
(a) is familiar with the subject equipment and the hazards involved 

with their application, use, administration and maintenance.

(b) is trained and authorized to de-energize, clear, ground, and tag 

circuits and equipment in accordance with established safety 

practices.

(c) is trained in the proper care and use of personal protective 

equipment such as rubber gloves, hard hat, safety glasses or face 

shields, arc-flash clothing, etc., in accordance with established 

safety practices.

(d) is trained to render first aid.
(e) has received safety training to recognize and avoid the hazards 

involved.

(f)  has the skills and knowledge pertaining to the construction and 

operation of this equipment and its installation.

IMPORTANT: 

These procedures do not claim to cover all possible 

details or variations encountered with the installation of a Surge 

Protective Device (SPD), nor do they provide for all possible 

conditions that may be encountered. If further information is 

desired or needed to address any particular issue not covered in this 

document, contact your Bussmann series product representative. 

The information in this document does not relieve the user from 

exercising good judgment, nor from using sound safety practices.

Note: 

Because Eaton has a policy of continuous product 

improvement, we reserve the right to change design specifications 

without notice. Should a conflict arise between the general 

information in this document and the contents of drawings or 

supplementary material, or both, the latter shall take precedence. 

For the latest version of this instruction manual, download 

Publication No. 10679 from Eaton.com/bussmannseries.
The contents of this installation manual are not part of, nor do they 

modify, any prior or existing agreement, commitment or relationship. 

The Bussmann Division terms and conditions of sale constitute 

the entire obligation of the Bussmann Division. The warranty in 

the terms and conditions of sale is the sole warranty from the 

Bussmann Division. Any statements in this document do not create 

new warranties or modify any existing warranty.

2.1 Safety concerns

This installation manual is not comprehensive. It is assumed the 

SPD installer will follow established safety procedures for working 

in an electrical environment. For more information on safety precau-

tions and procedures, consult the following websites:

• 

National Fire Protection Association (NFPA) www.nfpa.org

• 

Underwriters Laboratories (UL) www.ul.com

• 

National Electrical Mfgrs. Association (NEMA) www.nema.org

• 

American National Standards Association (ANSI) www.ansi.org

• 

Institute of Electrical and Electronics Engineers (IEEE)  

www.ieee.org

Summary of Contents for BUSSMAN Series

Page 1: ...MOV while supporting power frequency voltage The Type 2 BSPA models equipped with EMI filtering are designed to protect sensitive equipment from electrical noise Proper installation is critical to ensure the BSPA unit operates as intended The Type 1 BSPA units are intended for installation between the secondary of the service transformer and the lineside of the service equipment overcurrent protec...

Page 2: ... accordance with established safety practices d is trained to render first aid e has received safety training to recognize and avoid the hazards involved f has the skills and knowledge pertaining to the construction and operation of this equipment and its installation IMPORTANT These procedures do not claim to cover all possible details or variations encountered with the installation of a Surge Pr...

Page 3: ...identifies the unit s specifications and permits specifying any combination to meet requirements BSPA 200 208Y 8 P BSPA Product family Surge rating per phase Voltage system code Options NEMA enclosure For example BSPA unit catalog number BSPA200208Y8P where BSPA BSPA series 200 peak surge current rating 50 kA 200 kA 208Y voltage code and system configuration 8 feature option 1 8 P enclosure type N...

Page 4: ...S POSSIBLE SEE FIGURE 3 6 2 Panel mounted The preferred mounting of the BSPA is directly to the electrical panel with its integrated male connector hub and the supplied 3 4 trade size conduit locknut Insert the wires through the panel wall being careful not to damage the wire insulation Install the provided locknut and tighten to 20 3 lb in 2 3 N m If the installation requires the NEMA 4X rating i...

Page 5: ...ncluded 3 4 14 NPS external thread Locknut Mounting feet included 36 inch long wires 3 75 95 3 2 38 60 4 8 48 215 4 10 25 260 4 11 50 292 1 7 48 190 0 9 25 235 0 10 50 266 7 4X Ø 0 223 0 80 20 3 6 67 169 4 0 0747 THK 1 51 38 4 1 51 38 4 6 4 Enclosure mounting feet and dimensions The mounting feet attach to the bottom of the enclosure with the provided screws hardware to mount the feet to wall are ...

Page 6: ...C typically requiring a 1 pole for single phase systems 2 pole for split phase systems or 3 pole for 3 phase systems 30 A branch circuit breaker to protect BSPA conductors Twist and bind the wires of the BSPA unit tightly together To optimize BSPA performance minimize overall lead length To maximize performance for wire lengths longer than four inches phase wires should be twisted once for each fo...

Page 7: ... product distributor or Bussmann series product representative as the SPD may be damaged 8 3 Options audible alarm and Form C relay Note Using Form C contacts is optional Connection is not required for the proper BSPA operation The audible alarm and Form C relay are tied to the phase LEDs on the BSPA enclosure If protection to one or more phases is lost the following will occur Single split and 3 ...

Page 8: ...utlined in appropriate Bussmann Division selling policies or other contractual agreements between the parties This manual is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and the Bussmann Division NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FI...

Page 9: ...re to give any advice or recommendations by the Bussmann Division shall not constitute any warranty by or impose any liability upon the Bussmann Division AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY FITNESS FOR PURPOSE SOLD PRODUCTIVENESS OR ANY OTHER MATTER In no event shall the Bussmann Division be liable for special or consequential dam...

Page 10: ...t of Eaton CSA is a registered trademark of the Canadian Standards Group NEC is a registered trademark of the National Fire Protection Association UL is a registered trademark of the Underwriters Laboratories Inc Eaton 1000 Eaton Boulevard Cleveland OH 44122 Eaton com Bussmann Division 114 Old State Road Ellisville MO 63021 United States Eaton com bussmannseries 2017 Eaton All Rights Reserved Prin...

Reviews: