7 Measured value logging
7.3 Device data logging
46
BreakerVisu
06/16 MN01210001Z-EN
www.eaton.com
7.3.3 “Fast logging” option
If you enable the
Fast Logging
option for a device, you do not have to set a
scan rate (as you usually would otherwise). Enabling this option will turn the
device into a preferred device, meaning it will be put on the device priority
list. After that, data will be logged every 2 seconds.
7.3.4 How to find the log files
All log files are stored on the external storage device selected in the
Extras
screen in the case of the 7“ variant (SD card or USB flash drive) or on the
SD card in the case of the 3.5“ variant. These files can be used directly from
the external storage devices or downloaded for further processing using an
FTP client. BreakerVisu can generate deleted log files again.
The name syntax for the log file is as follows:
BV_data_[RTU oder SWD]_add[Geräteadresse]_[Jahr,Monat,Tag].csv