7 Measured value logging
7.1 Event logging
Event logging is a BreakerVisu program routine that runs in the background
and that is used to log the program‘s and all connected device‘ events. When
the program is started, when a circuit-breaker‘s trip state changes, when a
device changes status, or when a warning is issued for a device, the event
will be recorded in the event file. This event file is calendar day-based. In
other words, a day‘s events will be written to a file with the following name
syntax:
BV_events_[year,month,day].csv
Table 41: Event entry
The data that will be available in the event file will depend on the type of
devices that are connected. If there is no data for a specific type of file, the
corresponding placeholder will remain blank. Please note that event logging
is automatic and cannot be manually started or stopped.
The event file‘s name will follow the syntax below:
BV_events_[RTU oder SWD]_add[Geräteadresse]_[Jahr,Monat,Tag].csv
7.2 Energy logging
You can select the energy logging intervals you want. The energy data (active
power, in kWh) of all connected devices will be written to a file accordingly.
The file name will vary according to the configured logging interval
(
Table 42).
Column
Parameter
Description
Example
1
Date
Date when the event occurred
2014-03-27
2
Time
Time when the event occurred
08:49:55
3
field bus
Network to which the device is connected
Modbus-RTU
4
HW Addr.
The device's HW address on the network
1
5
Billing Site
Location name
As defined in the BreakerVisu configuration
Feeder #1
6
HW Type
Type of device
IZM26
7
Event
Type of event
Powered up
8
Trip Reason
Description of the event
Normal operating mode
9
State (Status)
The device's status
OPEN
10
I-L1 [A]
number
0.0
11
I-L2 [A]
number
0.0
12
I-L3 [A]
number
0.0
13
I-max [A]
number
“”
14
I-N [A]
number
0.0
15
I-GRD [A]
number
0.0