Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
1
C
Chhaapptteerr 11 IInnttrroodduuccttiioonn
11..11
IInnttrroodduuccttiioonn
The Eaton
®
BladeUPS® is an uninterruptible power system (UPS) that protects your sensitive electronic
equipment from the most common power problems, including power failures, power sags, power surges,
brownouts, and line noise.
Power outages can occur when you least expect it, and power quality can be erratic. These power problems
have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware—causing
hours of lost productivity and expensive repairs.
With the BladeUPS, you can safely eliminate the effects of power disturbances and guard the integrity of your
equipment. The BladeUPS is designed for critical applications such as ultra high-density blade servers in a data
center environment. Figure 1 shows the BladeUPS with an optional Extended Battery Module (EBM).
Figure 1. The BladeUPS Module with Optional EBM
Providing outstanding performance and reliability, unique BladeUPS benefits include the following:
•
High-density three-phase input, three-phase output UPS.
•
Scalability to 60 kW (redundant N+1 configuration) by connecting up to six additional BladeUPS modules. A
standalone UPS converts to a parallel UPS by changing the line cord and adding a communication card.
Each UPS in the parallel system connects to a BladeUPS Bar pre-installed in the rear of an Eaton rack.
Racks can be configured for bottom or top entry.
A Powerware Hot Sync
®
Controller Area Network (CAN) Bridge Card in each paralleled UPS provides
connectivity for system metering and operational mode control. In a parallel system that is not fully loaded,
each BladeUPS module will equally share the load. If the system loses input AC power, the system will
shift load to the UPSs with the strongest batteries to maximize runtime when on battery. Parallel systems
can be configured for capacity or redundancy and automatically increase redundancy as load levels
decrease in 12 kW steps.
Summary of Contents for BladeUPS none
Page 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Page 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Page 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Page 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Page 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Page 160: ...16420164914 164201649 14 ...