Access Power Solutions Installation Guide (APS6-400 Series)
30
Copyright © 2009-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-53B December 2010
Load CB
Rating
(Note 1)
Cable size
(Note 2)
2-hole Crimp Lug
(¼" studs, 5/8" spacing)
(Note 3)
Crimping tool
(Note 3)
5-15A
14 AWG
YAV10-2TC14
Y8MRB-1
20A
12 AWG
25-30A
10 AWG
40A
8 AWG
YA8CL-2TC14
Y1MR
50A
6 AWG
YA6CL-2TC14
60A
4 AWG
YA4CL-2TC14
80A
3 AWG
(Note 4)
YA3CL-2TC14
100A
1 AWG
YA1CL-2TC14
120A
1 AWG
YA1CL-2TC14
Notes:
1
See load circuit breaker derating factors on page
2
Minimum cable size. Does not allow for excessive voltage drop in long cable runs at high
current.
3
Part numbers are for FCI-BURNDY® products. In US/Canada use these parts or equivalent
UL-listed crimp lugs.
4
If 3 AWG cable is not available use 2 AWG cable and YA2CL-2TC14 crimp lug (Y1MR
crimping tool).
Step 3 - Check terminations, secure cables and test insulation
1
Check all terminations are correct and are tightened.
2
Secure the cables with cable ties to ensure there will be no strain on the terminals.
3
Test the insulation resistance of the cables.
Procedure complete
Task 6 - Install the Batteries
Always check that the battery cables have been terminated to the correct system polarity
BEFORE connecting the batteries or closing the battery disconnect device.
Connecting batteries to the system with incorrect system polarity will void all warranty
claims.
Installation procedure
Step 1 - Install the batteries
Follow the battery supplier's/manufacturer's installation instructions.