Access Power Solutions Installation Guide (APS6-400 Series)
22
Copyright © 2009-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-53B December 2010
Rectifier connections for
2 x 1W+N or 2 x 2W ac supply
Rectifier connections for
3 x 1W+N or 3 x 2W -wire ac supply
N/L2-L/L1 to Rectifier 1
N/L2-L/L1 to Rectifier 2
N/L2-L/L1 to Rectifier 3
N/L2-L/L1 to Rectifier 4
N/L2-L/L1 to Rectifier 5
N/L2-L/L1 to Rectifier 6
Procedure complete
Task 3 - Mount the APS in the Rack
Step 1 - Check clearances
APSs require the following minimum clearances for access and/or adequate air flow:
Front:
24" (600mm)
Rear:
If top access is unrestricted:
4” (100mm)
If top access is restricted:
24" (600mm)
Top:
3" (75mm) minimum from other equipment in the rack.