Product Specifications
9-2
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
www.eaton.com/powerquality
9.2.2
UPS Output
9.2.3
UPS Environmental
UPS Output Capacity
100% rated current
Output Voltage Regulation
± 1% (10% to 100% load)
Output Voltage
480 Vac Wye, 4W + ground
Output Voltage Harmonic Content
1% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
Output Voltage Balance
< 2% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
< 2.5
for 100% maximum load imbalance (linear load)
Frequency Regulation
0.1 Hz free running
Synchronous to Bypass
± 4 Hz (default setting)
Frequency Slew Rate
1 Hz per second (default setting)
Load Compatibility
0.8 pF Leading
0.8 pF Lagging
Overload Capability
<110% for 10 minutes
<125% for 60 seconds
<150% for 10 seconds
>150% for 300 milliseconds
Operating Temperature
5 to 40
C (41 to 104
F) without derating. The recommended operating
temperature is 25
C (77
F).
Operating Altitude
Maximum 1500m (5000 ft) at 40
C without derating
Storage Temperature
25 to +55
C, excluding batteries (prolonged storage above 40
C causes
rapid battery self-discharge)
Relative Humidity (operating and
storage)
95%, noncondensing
Acoustical Noise
50 kW at 100% load – 65 dBA at a 1m distance, per ISO 7779
Agency Markings
UL 924 Auxiliary Lighting and Power Equipment
Safety: UL1778 4th Ed./CSA22.2 No. 107.3 2nd Ed.
EMI Emissions and Immunity
Meets IEC 62040-2 C3 and FCC Part 15 Subpart B, ICES-003, CISPR 22, VCCI:
Class A, and CISPR 24.
Electrostatic Discharge (ESD)
Immunity
Meets IEC 61000-4-2 Level 3 specifications. Withstands up to 4 kV contact
pulse without damage and with no disturbance or adverse effect to the
critical load.
Summary of Contents for 93PM UPS
Page 1: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 25: ...Section 1 Installation...
Page 26: ......
Page 87: ...Section 2 Operation...
Page 88: ......
Page 145: ......
Page 146: ...P 164000540 4 P 164000540 4...