Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
www.eaton.com/powerquality
9-1
Chapter 9
Product Specifications
9.1
Model Numbers
The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
9.2
Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
9.2.1
UPS Input
Model
Power Rating
Frequency
Eaton 93PM-50-1
Eaton 93PM-50-2 (N+1)
20 kW
50/60 Hz
Eaton 93PM-50-1
Eaton 93PM-50-2 (N+1)
30 kW
50/60 Hz
Eaton 93PM-50-1
Eaton 93PM-50-2 (N+1)
40 kW
50/60 Hz
Eaton 93PM-50-1
Eaton 93PM-50-2 (N+1)
50 kW
50/60 Hz
Operating Input Voltage
Rectifier: 480 Vac Wye, 3W + ground. Neutral not used.
Bypass: 480 Vac Wye, 4W + ground.
Operating Input Frequency Range
50/60 Hz
Operating Input Current
Reduced for Generator
Adjustable
Input Current Harmonic Content
3% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801
4
Battery Voltage
240 cell – 480 Vdc
Battery Charging Capacity
16.5 A maximum per 50 kW module at full load at nominal input voltage
Summary of Contents for 93PM UPS
Page 1: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 25: ...Section 1 Installation...
Page 26: ......
Page 87: ...Section 2 Operation...
Page 88: ......
Page 145: ......
Page 146: ...P 164000540 4 P 164000540 4...