56
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
Figure 20. Removing the UPS Pallet Skids and Supports
Cabinet
Mounting Bolts
(4 places front)
(4 places rear)
Skid Mounting Bolts
(4 places front)
(4 places rear)
Floor Protectors
(2 places front)
(2 places rear)
Right Side
Cabinet Support
Jacking Bolts
(2 places front)
(2 places rear)
Front Cabinet
Support
Pallet Skid
Left Side
Cabinet Support
Rear Cabinet
Support
Cabinet
Support Bolts
(2 places at
each corner)
WARNING
Do not remove or loosen the cabinet mounting or cabinet support bolts until instructed. If unpacking and
unloading instructions are not closely followed, the cabinet may tip and cause serious injury or death.
4.
Loosen, but do not remove, the skid mounting bolts holding the pallet skids to the front and rear supports,
and to the left and right side supports.
5.
If a sidecar is attached to the UPS, loosen, but do not remove, the sidecar skid mounting bolts holding the
sidecar pallet skids to the sidecar front and rear supports, and to the left and right supports (see
for the Top Entry Sidecar or
for the Bypass Sidecar (SIAC-B).
WARNING
RISK OF INSTABILITY. Turning the jacking bolts unevenly may cause the cabinet to become unbalanced. To
prevent tipping the cabinet, raise the cabinet no more than 3 mm (1/8") above the floor (just enough to allow the
removal of the pallet skids). Failure to follow these instructions can result in serious injury or death.
Summary of Contents for 93PM-L Series
Page 4: ......
Page 164: ...P 16400071103 P 164000711 03...