Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
149
C
Chhaapptteerr 99 P
Prroodduucctt S
Sppeecciiffiiccaattiioonnss
99..11
M
Mooddeellss
The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
Model
Power Rating
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1)
10 kW
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1)
20 kW
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1)
30 kW
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1)
40 kW
Eaton 93PM-L 60-3
50 kW
Eaton 93PM-L 60-3
60 kW
99..22
S
Sppeecciiffiiccaattiioonnss
The following sections detail the input, output, environmental, and battery specifications for the UPS.
99..22..11
U
UP
PS
S IInnppuutt
Operating Input Voltage
Rectifier: 208 or 220 Vac Wye, 3W + ground. Neutral not used.
Bypass: 208 or 220 Vac Wye, 4W + ground.
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See
through .
Reduced for Generator
Adjustable
Input Current Harmonic Content
≤ 3.5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
Battery Voltage
240 cell – 480Vdc
Battery Charging Capacity
7 A maximum per 20 kW module at full load at nominal input voltage
99..22..22
U
UP
PS
S O
Ouuttppuutt
UPS Output Capacity
100% rated current
Output Voltage Regulation
± 1% (10% to 100% load)