Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
Figure 35. Main Elements of the UPS System
Battery
Switchgear
Battery
Converter
Rectifier
Inverter
Inverter
Switchgear
Power Module
Rectifier
Switchgear
AC Input to
Rectifier /
Charger
AC Input to
Bypass
Static
Switch
Digital
Metering
Battery
AC Output
to Critcal
Load
UPS Cabinet
55..22
S
Siinnggllee U
UP
PS
S
A single UPS operates independently to support an applied load from the inverter, providing conditioned and
uninterruptible AC power to the critical load from the output of the module. During an outage, the inverter
continues to operate, supporting power to the load from the battery supply. If the unit requires service, applied
loads are transferred to the internal bypass either automatically or manually. With the exception of an optional
external battery cabinet, no other cabinets or equipment are required for the single UPS to successfully support
its applied loads.
55..22..11
M
Mooddeess
The Eaton 93PM-L UPS supports a critical load in four different modes of operation:
•
In Energy Saver System (ESS) mode, commercial AC power is supplied directly to the critical load through
the internal bypass and transfers automatically to Normal mode (double-conversion on demand) if an
abnormal condition is detected. The battery charger also provides charging current for the battery, if
needed.
•
In Normal (double-conversion) mode, the critical load is supplied by the inverter, which derives its power
from rectified utility AC power. In this mode, the battery charger also provides charging current for the
battery, if needed.
•
In Bypass mode, the critical load is directly supported by utility power. The battery charger also provides
charging current for the battery, if needed.