Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
Table 27. Normally-Open REPO Connections and Wire Terminations
From REPO
Station
Switch Con-
tact Block
(Either Block)
UPS REPO
Terminal
Name
Description
Recom-
mended
Minimum
Wire Size
Size of
Wire
Termina-
tion
Tightening
Torque
3 NO
3
EPO_A
Input: Normally-open dry contact
used to activate UPS EPO from a
remote switch
Twisted Pair
Wires #18
AWG
#16
#30 AWG
2 lb in
(0.22-
0.25 Nm)
4 NO
4
EPO_B
Figure 33. Normally-Open REPO Switch Wiring
3
1
2
4
3
4
Table 28. Normally-Closed REPO Connections and Wire Terminations
From REPO
Station
Switch Con-
tact Block
(Either Block)
UPS REPO
Terminal
Name
Description
Recom-
mended
Minimum
Wire Size
Size of
Wire
Termi-
nation
Tighten-
ing
Torque
3 NO
1
EPO_A_B
Input: Normally-closed dry
contact used to activate UPS
EPO from a remote switch
Twisted
Pair Wires
#18 AWG
#16
#30 AWG
2 lb in
(0.22-
0.25 Nm)
4 NO
2
GND-ISO