Installation Plan and Unpacking
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7
www.eaton.com/powerquality
3-15
For three-wire SIAC-B external power wiring requirements, including the minimum AWG size of external
wiring, see Table 3-2 or Table 3-3. Wire sizes listed are for copper wiring only.
Table 3-2. External Power Wiring Requirements for the Eaton 93PM 150 kW Three-Wire SIAC-B and 93PM 200 kW
Three-Wire SIAC-B – Two and Three Breaker Maintenance Bypass
Basic Unit Rating
Units
Rating 60 Hz
kW
150
200
Input/Output Voltage
Volts
480/480
480/480
AC Input to
Maintenance Bypass
(3) Phases, (1) Ground
A
Maximum Amps
218
291
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
2/0
(2)
4/0
(2)
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil
(each)
4
(1)
3
(1)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Ground
C
Maximum Amps
180
240
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
1
(2)
2/0
(2)
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil
(each)
4
(1)
3
(1)
Building and Inter-Cabinet Ground
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil
(each)
4
(1)
4
(1)
NOTE
Callout letters
A
and
C