90
Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
Figure 49. One PM, Common Rectifier Feed, Common Battery, Dual-Feed Configuration
Minislot
Interface
E1, E2, E3
E6, E7, E8
48V Battery
UVR
UPS
CABINET
AC Output to
Critical Load
E9,
E10,
E11
Static
Switch
AC Input to
UPS Rectifier
3 Wire A-B-C
Rotation
AC Input to
Bypass
3 Wire A-B-C
Rotation
Interface Board
Battery Aux
Remote EPO
Building Alarms
Alarm Relays
Fuse
Battery
Converter
Inverter
Fuse
Rectifier
Input
Contactor
(K1)
Fuse
PM
Battery
Breaker
BATTERY SYSTEM
E4, E5
(Not supplied with the UPS)
A
B
C
D
Single-Feed Kit
EXTERNAL
BATTERY
CABINET
NOTE
AC input to rectifier is not used in single feed configuration. Dashed lines indicate optional features/components
NOTE
Customer supplied bypass input breaker with 48-60VDC UVR is required unless I/O cabinet with Bypass Contactor is selected.
NOTE
Callout letters
A
,
B
,
C
, and
D
map to the 480V Input/Output Ratings and External Wiring Requirements Table in Chapter 3.
(optional)
K5