13. Verify that no alarms appear on the UPS front panel display.
If the
indicator is flashing, do not proceed until all alarms are clear. Check the UPS status from the
front panel to view the active alarms. Correct the alarms and restart if necessary.
14. Verify the phase rotation for each UPS.
15. From the UPS Status menu, select the Units on CAN Bus option and verify that all UPSs appear in the list.
If all UPSs appear in the list, press the
ESC
button until the Eaton logo or Mimic screen appears.
If any UPS is missing, verify the Powerware Hot Sync CAN Bridge Card connections and recheck the
status from the UPS front panel.
16. Press the
button on the front panel display and then press the
button to select the TURN UPS ON/
OFF menu.
17. Select the System On option; press and hold the
button for three seconds, until the UPS stops
beeping.
The UPS goes to Bypass mode for five seconds, and then the
indicator illuminates. Each UPS
should be in Normal mode.
18. Press the
ESC
button until the Eaton logo or Mimic screen appears.
66..33
C
Coonnffiigguurriinngg tthhee U
UP
PS
S ffoorr EEB
BM
Mss
NOTE
Each UPS in a parallel system must have its own EBM and the same number of EBMs
to ensure consistent runtimes.
To ensure maximum battery runtime, configure the UPS for the correct number of EBMs:
1.
Press any button on the front panel display to activate the menu options.
2.
Using the
OPERATION
Eaton 9355 Parallel UPS (10/15 kVA) User's Guide
S
164201601 Rev B
56
The following table shows the indicator status and description.
Indicator
Status
Description
Green
On
The UPS is operating normally.
Flashing
S
The UPS is starting up or is shut down and waiting for power to return.
S
A new information message is active.
S
Bypass is not available.
Off
The UPS is turned off and will not turn on automatically.
Yellow
On
The UPS is in Battery mode.
Yellow
On
The UPS is in Bypass mode.
Red
On
The UPS has an active alarm.
Flashing
There is a new UPS alarm condition. See “Troubleshooting” on page 67 for
additional information.
Changing the Language
Press and hold the first button on the left for approximately five seconds
to select the language menu. This action is possible from any LCD menu
screen.
Display Functions
As the default or after 15 minutes of inactivity, the LCD displays the
selectable startup screen. The default is the Eaton logo and can be
changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press
any button to restore the screen.
Use the two middle buttons ( and ) to scroll through the menu
structure. Press the
button to enter a submenu. Press the
button
to select an option. Press the
ESC
button to cancel or return to the
previous menu.
button, scroll to the Settings menu.
3.
Press the
OPERATION
Eaton 9355 Parallel UPS (10/15 kVA) User's Guide
S
164201601 Rev B
56
The following table shows the indicator status and description.
Indicator
Status
Description
Green
On
The UPS is operating normally.
Flashing
S
The UPS is starting up or is shut down and waiting for power to return.
S
A new information message is active.
S
Bypass is not available.
Off
The UPS is turned off and will not turn on automatically.
Yellow
On
The UPS is in Battery mode.
Yellow
On
The UPS is in Bypass mode.
Red
On
The UPS has an active alarm.
Flashing
There is a new UPS alarm condition. See “Troubleshooting” on page 67 for
additional information.
Changing the Language
Press and hold the first button on the left for approximately five seconds
to select the language menu. This action is possible from any LCD menu
screen.
Display Functions
As the default or after 15 minutes of inactivity, the LCD displays the
selectable startup screen. The default is the Eaton logo and can be
changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press
any button to restore the screen.
Use the two middle buttons ( and ) to scroll through the menu
structure. Press the
button to enter a submenu. Press the
button
to select an option. Press the
ESC
button to cancel or return to the
previous menu.
button twice to select the User Settings menu.
4.
Using the
OPERATION
Eaton 9355 UPS (10/15 kVA) User's Guide
S
164201594 Rev D
82
The following table shows the indicator status and description.
Indicator
Status
Description
Green
On
The UPS is operating normally.
Flashing
S
The UPS is starting up or is shut down and waiting for power to return.
S
A new information message is active.
S
Bypass is not available.
Off
The UPS is turned off and will not turn on automatically.
Yellow
On
The UPS is in Battery mode.
Yellow
On
The UPS is in Bypass mode.
Red
On
The UPS has an active alarm.
Flashing
There is a new UPS alarm condition. See “Troubleshooting” on page 105 for
additional information.
Changing the Language
Press and hold the first button on the left for approximately five seconds
to select the language menu. This action is possible from any LCD menu
screen.
Display Functions
As the default or after 15 minutes of inactivity, the LCD displays the
selectable startup screen. The default is the Eaton logo and can be
changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press
any button to restore the screen.
Use the two middle buttons ( and ) to scroll through the menu
structure. Press the
button to enter a submenu. Press the
button
to select an option. Press the
ESC
button to cancel or return to the
previous menu.
button, scroll to the Battery Setup option and press the
OPERATION
Eaton 9355 UPS (10/15 kVA) User's Guide
S
164201594 Rev D
82
The following table shows the indicator status and description.
Indicator
Status
Description
Green
On
The UPS is operating normally.
Flashing
S
The UPS is starting up or is shut down and waiting for power to return.
S
A new information message is active.
S
Bypass is not available.
Off
The UPS is turned off and will not turn on automatically.
Yellow
On
The UPS is in Battery mode.
Yellow
On
The UPS is in Bypass mode.
Red
On
The UPS has an active alarm.
Flashing
There is a new UPS alarm condition. See “Troubleshooting” on page 105 for
additional information.
Changing the Language
Press and hold the first button on the left for approximately five seconds
to select the language menu. This action is possible from any LCD menu
screen.
Display Functions
As the default or after 15 minutes of inactivity, the LCD displays the
selectable startup screen. The default is the Eaton logo and can be
changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press
any button to restore the screen.
Use the two middle buttons ( and ) to scroll through the menu
structure. Press the
button to enter a submenu. Press the
button
to select an option. Press the
ESC
button to cancel or return to the
previous menu.
button.
5.
Use the
OPERATION
Eaton 9355 Parallel UPS (10/15 kVA) User's Guide
S
164201601 Rev B
56
The following table shows the indicator status and description.
Indicator
Status
Description
Green
On
The UPS is operating normally.
Flashing
S
The UPS is starting up or is shut down and waiting for power to return.
S
A new information message is active.
S
Bypass is not available.
Off
The UPS is turned off and will not turn on automatically.
Yellow
On
The UPS is in Battery mode.
Yellow
On
The UPS is in Bypass mode.
Red
On
The UPS has an active alarm.
Flashing
There is a new UPS alarm condition. See “Troubleshooting” on page 67 for
additional information.
Changing the Language
Press and hold the first button on the left for approximately five seconds
to select the language menu. This action is possible from any LCD menu
screen.
Display Functions
As the default or after 15 minutes of inactivity, the LCD displays the
selectable startup screen. The default is the Eaton logo and can be
changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press
any button to restore the screen.
Use the two middle buttons ( and ) to scroll through the menu
structure. Press the
button to enter a submenu. Press the
button
to select an option. Press the
ESC
button to cancel or return to the
previous menu.
or
OPERATION
Eaton 9355 Parallel UPS (10/15 kVA) User's Guide
S
164201601 Rev B
56
The following table shows the indicator status and description.
Indicator
Status
Description
Green
On
The UPS is operating normally.
Flashing
S
The UPS is starting up or is shut down and waiting for power to return.
S
A new information message is active.
S
Bypass is not available.
Off
The UPS is turned off and will not turn on automatically.
Yellow
On
The UPS is in Battery mode.
Yellow
On
The UPS is in Bypass mode.
Red
On
The UPS has an active alarm.
Flashing
There is a new UPS alarm condition. See “Troubleshooting” on page 67 for
additional information.
Changing the Language
Press and hold the first button on the left for approximately five seconds
to select the language menu. This action is possible from any LCD menu
screen.
Display Functions
As the default or after 15 minutes of inactivity, the LCD displays the
selectable startup screen. The default is the Eaton logo and can be
changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press
any button to restore the screen.
Use the two middle buttons ( and ) to scroll through the menu
structure. Press the
button to enter a submenu. Press the
button
to select an option. Press the
ESC
button to cancel or return to the
previous menu.
buttons to select the number of strings according to your UPS configuration:
All 2-High UPS and EBM Cabinets*
Number of Strings
UPS + 1 EBM
6
UPS + 2 EBMs
10
UPS + 3 EBMs
14
UPS + 4 EBMs
18
All 3-High UPS and EBM Cabinets*
Number of Strings
UPS + 1 EBM
10
UPS + 2 EBMs
16
Summary of Contents for 9355 Series
Page 1: ...p n 164201601 Revision E0 10 15 kVA User s Guide Eaton 9355 Parallel UPS ...
Page 4: ......
Page 10: ...x Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 List of Tables ...
Page 18: ...8 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 Safety Warnings ...
Page 54: ...44 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 UPS System Installation ...
Page 68: ...58 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 Operation ...
Page 72: ...164201601E0 164201601 E0 ...