COMMUNICATION
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
S
164201642 Rev C
www.eaton.com/powerquality
70
Relay Output Contacts
The UPS incorporates a programmable relay output with potential free
contacts for remote alarm indications (see Figure 28 on page 55). An
additional four relay outputs can be obtained with the X-Slot compatible
Relay Interface Card.
W
A
R
N
I
N
G
The relay output contacts must not be connected to any utility connected circuits. Reinforced
insulation to the utility is required. The relay output contacts must have a maximum rating of
30 Vac/1A and 60 Vdc/2A nominal values.
Programmable Signal Inputs
The UPS incorporates two programmable signal inputs (see Figure 28 on
page 55). Use of non-polar (relay) control input is recommended. The
pins must be shorted with maximum resistance of 10 ohm in order to
activate the specific input.
NOTE
See Figure 39 on page 68 for the polarity and verify these connections if polarity
control is required.
The default and programmable settings for the signal inputs are shown
in Table 8.