Installation Plan and Unpacking
2-6
Eaton 9315/9390/9395/9395P Fixed Primary Sync Control Installation and Operation Manual
P-164000023—Rev 03
2.2.2
Eaton Fixed Primary Sync Control and Primary Interface Wiring Preparation
Read and understand the following notes while planning and performing the installation:
l
Refer to national and local electrical codes for acceptable external wiring practices.
l
Material and labor for external wiring requirements are to be provided by designated personnel.
l
For external wiring, use 90°C copper wire with a minimum insulation rating of 600V. If wire is run in an
ambient temperature greater than 30°C, higher temperature wire and/or larger size wire may be necessary.
See the applicable wiring information in Table 3-2, Table 3-3, or Table 3-4 for the Eaton 9315 UPS, Table 3-7
on page 3-16 for the Eaton 9390 UPS, in Table 3-8 on page 3-20 for the Power Xpert 9395 UPS, and
Table 3-10 and Table 3-11 for Power Xpert 9395P.
l
Use 14 AWG wiring with a minimum insulation rating of 600V for interconnections between the Eaton Fixed
Primary Sync Control, the Primary Interface enclosure, the UPS, and the customer remote monitoring
system.
l
Use Class 1 wiring methods (as defined by the NEC) for interface wiring up to 30V. The wire should be rated
at 24V, 1A minimum.
l
Use Class 2 wiring methods (as defined by the NEC) for interface wiring from 30 to 600V. The wire should
be rated at 600V, 1A minimum and 12 AWG maximum.
l
Sync Control dry contacts are rated at 5.30 Vdc/250 Vac at 2A per contact (maximum load).
l
Conduit must be used when installing external wiring between the Eaton Fixed Primary Sync Control,
Primary Interface, and the UPS.
l
The Eaton Fixed Primary Sync Control can be installed up to a maximum of 152.4m (500 ft) from the UPS
system.
CAUTION
When connecting the bypass and load voltage from another model UPS to an Eaton 9390, Power
Xpert 9395 UPS, or Power Xpert 9395P UPS using the Eaton Fixed Primary Sync Control
accessory, use Phase A, Phase B, and Neutral connections from the other UPS. DO NOT connect
the other model UPS Phase C bypass and load voltage to the Sync Control connection point when
connecting to an Eaton 9390, Power Xpert 9395 or Power Xpert 9395P UPS.
2.3
Inspecting and Unpacking the Eaton Fixed Primary Sync Control or Primary Interface
The unit arrives covered with protective packaging material.
1.
Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION
Do not install a damaged cabinet. Report any damage to the carrier and contact Eaton service
representative immediately.
2.
Remove the protective cardboard covering from the Eaton Fixed Primary Sync Control or Primary Interface
unit by cutting where indicated using a knife blade no longer than 25 mm (1”).
3.
Remove the plastic bag and foam packing material, and discard or recycle them in a responsible manner.
Summary of Contents for 9315P
Page 1: ...Eaton 9315 9390 9395 9395P Fixed Primary Sync Control Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 9315 9390 9395 9395P Fixed Primary Sync Control Installation and Operation Manual...
Page 8: ...This page intentionally left blank...
Page 61: ......
Page 62: ...P 164000023 2 P 164000023 3...