Bypass input and output overcurrent protection and bypass, output and
accessory disconnect switches must be provided by the user.
4.5
Unpack and unload the UPS
Before you start to unpack and unload the UPS, look at the TipNTell indicator on
the package surface. When you have unpacked and unloaded the UPS, look at
the DropNTell indicator on the back of the UPS. If the equipment has been
correctly transported in the upright position, the indicators should be intact. If the
TipNTell indicator arrow has turned all blue or the arrow head(s) of the DropNTell
are black, contact the appropriate parties to report inappropriate transportation.
WARNING
The UPS cabinet is heavy. If you do not obey the unpacking instructions,
the cabinet may tip over and cause serious injury.
Do not tilt the UPS cabinet more than 10 degrees from the vertical or the
cabinet may tip over.
For transportation purposes, the UPS cabinet is bolted onto a wooden pallet. To
remove the pallet, do the following:
1.
Before you unload the cabinet from the pallet, use a forklift or other material
handling equipment to move the cabinet to the installation area. Insert the
forks of the forklift between the skids on the bottom of the unit.