Automatic Standby Generator Owner’s Manual
19
Section 4
Maintenance
NOTE: Proper maintenance and proper and safe operation is crucial to the life of the generator. Genuine Generac parts MUST be used
to ensure warranty coverage.
NOTE: Since most maintenance alerts will occur at the same time (most have two year intervals), only one will appear on the Control
Panel display at any one time. Once the first alert is cleared, the next active alert will be displayed.
All service to this generator must be performed by a qualified service person only.
4.1 — Performing Scheduled Maintenance
t is important to perform Maintenance as specified in the Service Schedule for proper generator operation and to ensure that the generator com-
plies with the applicable emission standards for the duration of its useful life. Service and repairs may be performed by any qualified service per-
son or repair shop. Additionally, emissions critical maintenance must be performed as scheduled in order for the Emissions Warranty to be valid.
Emissions critical maintenance consists of servicing the air filter and spark plugs in accordance with the Service Schedule. The controller will
prompt for Schedule A or Schedule B maintenance to be performed. Schedule A maintenance consists of the oil, oil filter and tune-up. Schedule
B maintenance includes the oil, oil filter, tune-up, air cleaner, spark plug(s) and valve clearance.
4.2 — Service Schedule
ATTENTION: All service work must be performed by a qualified service person only.
System Component
Procedure
Frequency
X = Action
R= Replace as Necessary
* = Notify Dealer if Repair is Needed
Inspect
Change Clean
W = Weekly
M = Monthly
Y = Yearly
Fuel
Fuel lines and connections*
X
M
Lubrication
Oil level
X
M or 24 hours of continuous operation
Oil
X
2Y or 200 hours of operation**
Oil filter
X
2Y or 200 hours of operation**
Cooling
Enclosure louvers
X
X
W
Battery
Remove corrosion, ensure dryness
X
X
Y
Clean and tighten battery terminals
X
X
Y
Check charge state
X
R
Y
Electrolyte level (unsealed batteries only)*
X
R
Every 6 M
Engine and Mounting
Air cleaner
X
R
400 hours
Spark plug(s)
X
R
400 hours
Valve Clearance
X
400 hours***
General Condition
Vibration, Noise, Leakage*
X
M
Complete Tune-Up*
To be completed by a Dealer
2Y or 200 hours
* Contact the nearest Dealer for assistance if necessary.
** Change oil and filter after the first 25 hours of operation. Continue to check at intervals of 200 hours, or 2 years, whichever occurs first.
Change sooner when operating under a heavy load or in a dusty or dirty environment or in high ambient temperatures.
*** Check valve clearance after the first 25 hours of operation. Continue to check at intervals of 400 hours.
*
Summary of Contents for 8 kW Air-cooled
Page 4: ...iii This page intentionally left blank...
Page 14: ...10 Automatic Standby Generator Owner s Manual This page intentionally left blank...
Page 22: ...18 Automatic Standby Generator Owner s Manual This page intentionally left blank...
Page 32: ...28 Automatic Standby Generator Owner s Manual This page intentionally left blank...
Page 35: ......