![Eaton 5PXEBM48RTG2 Advanced User'S Manual Download Page 33](http://html1.mh-extra.com/html/eaton/5pxebm48rtg2/5pxebm48rtg2_advanced-users-manual_525008033.webp)
614-40099-00
33
1.
2.
1.
2.
3.
•
•
•
•
•
6.5 Replacing the UPS equipped with a HotSwap MBP
The HotSwap MBP module makes it possible to service
or even replace the UPS without affecting the
connected loads (HotSwap function).
Maintenance
Set switch (45) to Bypass position. The red LED on the
HotSwap MBP module goes ON, indicating that
the load is supplied directly with AC input source
power.
Stop the UPS by pressing the
button on the UPS
control panel. LED (43) "UPS ON - OK to switch" goes
OFF, the UPS can now be disconnected and replaced.
Return to normal operation
Check that the UPS is correctly connected to the
HotSwap MBP module.
Start the UPS by pressing the
button on the UPS
control panel. LED (43) "UPS ON - OK to switch"
on the HotSwap MBP module goes ON (otherwise,
there is a connection error
between the HotSwap MBP module and the UPS).
Set switch (45) to Normal position. The red LED on
the HotSwap MBP module goes OFF.
6.6 Recycling the used equipment
Contact your local recycling or hazardous waste center for information on proper disposal of the used equipment.
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is
required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be
toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid batteries
and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous
waste center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact
your local recycling/reuse or hazardous waste center.
7 Troubleshooting
The Eaton 5PX is designed for reliable, autonomous operation while providing you with notifications and alerts whenever
a potential operational or performance issue occurs.
Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are
preventive alarms intended to alert the user.
Events are silent status information that are recorded into the Event log. Example = "AC freq in range".
Alarms are recorded into the Event log and displayed on the LCD status screen with the logo blinking. Some alarms
may be announced by a beep every 3 seconds. Example = "Battery low".
Faults are announced by a continuous beep and red LED, recorded into the Fault log and displayed on the LCD with a
specific message box. Example = Out. short circuit.