UPS start-up with the HotSwap MBP module
1. Check that the UPS is correctly connected to the HotSwap MBP module.
2. Set switch (45) to Normal position.
3. Start the UPS by pressing the ON/OFF button on the UPS control panel. The load is supplied by the UPS.
LED (43) "UPS ON - OK to switch" on the HotSwap MBP module goes ON.
HotSwap MBP module test
1. Set switch (45) to Bypass position and check that the load is still supplied.
2. Set switch (45) back to Normal position.
4 Interfaces and Communication
4.1 Control panel
The screen provides useful information about the UPS itself, load status, events, measurements and settings.
The LED bar
⑨
has been implemented to provide a quick visual reference of UPS status "at-a-glance".
①
Power ON indicator (green)
②
On battery indicator (yellow)
③
Alarm Indicator (red)
④
Escape
⑤
Up
⑥
Down
⑦
Enter
⑧
On/Off button
⑨
Led bar