![Eaton Holec Clink II User Manual Download Page 74](http://html1.mh-extra.com/html/eaton-holec/clink-ii/clink-ii_user-manual_3683038074.webp)
CLINK II SCU MANAGER
technical specifications scu
version 5.0
74
8.4.4
Analog output
The SCU has 1 unipolar analog output, with description A0_0. For information regarding the function of the
analog output see table 22 on page 29.
Technical specifications
Transient
150
Vmsec
Vmax = 150
V
Overload
Short circuit proof from -30 V..
+30 V with respect to Gnd
Vdc
Table 70: Technical specifications analog outputs
Name
Specification
Unit
Note
Type
Current, unipolar
Burden resistance
0-900
Ohm
Nominal burden resistance
500
Ohm
Nominal supply voltage
24
Vdc
Max. supply voltage
30
Vdc
Min. supply voltage
- 0.6
Vdc
Output voltage
0-10
Vdc
at 0-20 mAdc
(Rb = 500 Ohm).
Transient
150
Vmsec
Vmax = 150
V
Table 69: Technical specifications digital outputs
Name
Specification
Unit