Peer to Peer v2.1
7
Prerequisites
1.
CPT Tool dated 6
th
Dec 2018 or later.
2.
FG Series firmware version v1.5b50 or later (EasyIO FG) and v2.0b50 or later for (EasyIO FG+) is required for
best performance.
3.
For FS Series, firmware has to be V3.0b50 or later.
4.
For FW Series, firmware has to be V1.0b12d or later.
5.
For FT Series, firmware has to be V2.1b11 or later.
6.
Minimum 2 or more controllers running P2P service in the same subnet.
If there is only one controller running in the same subnet, the broadcast status will be down.
Sync the Controller Time
Failure to perform this will caused the P2P not to run properly.
Step 1
Double click the “
service”
folder to display all the service objects.
Single clicking the
“time”
object displays the time object property view in the Right pane of the CPT Tool view.
Double clicking the
“time”
object opens a new window where configuration of the FG Series Controller RTC is
possible.
Step 2
Double click the
“time”
object.
In the
New Date Time
window select the
“Configuration”
radio button and click the “
LocalTime
” button.
Step 3
Click the
Save
button in the
New Date Time
window. The controller RTC should now be synced with your
computer’s time, inclusive of the
Time Zone
. This can be verified by reviewing the
“Sedona Date Time”
option.