Eastron SDM630MCT-2L User Manual Download Page 1

User Manual 

2020

SDM630MCT-2L 

DIN Rail Smart Energy Meter for Single and Three 

Phase Electrical Systems 

 

1

 

Introduction

This document provides operating, maintenance and installation 
instructions. This unit measures and displays the characteristics of 
Single Phase Two Wire (1P2W) and 2 x (C1 & C2) Three Phase Four 
Wire (3P4W) networks. The measuring parameters include Voltage 
(V), Current (A), Frequency (Hz), Power (kW/KVA/KVAr), Power 
Factor (PF), Imported, Exported and Total Energy (kWh/kVArh). The 
unit also measures Maximum Demand Current and Power, this is 
measured over preset periods of up to 60 minutes. 

This particular model accommodates 100mA Current Transformers 
and can be configured to work with a wide range of CTs. It also 
comes with a complete comms capability with built in RS485 
Modbus RTU outputs, configuration is password protected.

This unit can be powered from a separate auxiliary supply (AC or 
DC). Alternatively, it can be powered from the monitored supply by 
linking the voltage reference and neutral reference in to terminals 5 
& 6 (Please refer to wiring diagram).

1.1

 Unit Characteristics

The SDM630MCT-2Lcan measure and display 2 x Three Phase 
circuits (C1 & C2) :

• Phase to Neutral Voltage and THD% (Total Harmonic Distortion) 

of all Phases

• Line Frequency
• Current, Maximum Demand Current and Current THD% of all 

Phases

• Power, Maximum Power Demand and Power Factor
• Imported, Exported & Total Active Energy
• Imported, Exported & Total Reactive Energy

The unit has a Password-Protected set up menu for:

• Changing the Password
• System Configuration - 1P2W & 3P4W.
• Demand Interval Time
• Reset for Demand Measurements

1.2

 Current Transformer Primary Current

This unit requires configuring to operate with the appropriate 
curren transformer(s), thesecondary current is 0.1A. It is 
programmed by inputting the ratio (CT Primary). It can be used on 
primary currents up to 6000A. 

1.3

 RS485 Serial – Modbus RTU

This unit is compatible with remote monitoring through RS485 
Modbus RTU. Set-up screens are provided for configuring the 
RS485 port. Refers to section 4.8.

2

 Start Up Screens

The first screen lights  

up all display segments 

and can be used as a 

display check.

The second screen 

indicates the firmware 

installed in the unit and  

its build number. 

The interface performs a 

self-test and indicates the 

result if the test passes.

*After a short delay, the screen will display active  
energy measurements.

3

 Measurements 

The buttons operate as follows:

ESC

U/I

Selects the Voltage and Current display 

screens. In Set-up Mode, this is the  

“Left” (press) or “Escape” (hold 3sec) 

button.

Select the Frequency and Power factor 

display screens. In Set-up Mode, this is 

the “Up” (press) button.

Select the Power display  screens.  

In Set-up Mode, this is the  

“Down” (press) button.

Select the Energy display screens.  

In Set-up mode, this is the  

“Right” (press) or “Enter” (hold 3sec) 

button.

3.1 

Switching Three Phase Circuit Display

Default is Circuit 1 (C1).

 

To Switch from Circuit 1 (C1) 

to Circuit 2 (C2) press and 

hold the 

 button. Press 

and hold again to switch 

back to C1.

 

3.1.1

 Voltage and Current

Each successive press of the 

ESC

U/I

 button selects a new parameter:

Phase to neutral voltages.

Phase to Phase voltages.

Current on each phase.

Phase to neutral voltage 

THD%.

Current THD% for each 

phase.

3.2

 Frequency and Power Factor and Demand 

Each successive press of the 

 button selects a new range:

Frequency and Power 

Factor (total).

Power Factor of each 

phase.

Maximum Power Demand.

Maximum Current 

Demand.

3.3 

Power 

Each successive press of the 

 button select a new range:

Instantaneous Active 

Power in kW.

Instantaneous Reactive 

Power in kVAr.

Instantaneous Volt-Amps 

in KVA.

Total kW, kVArh, kVA.

3.4

 Energy Measurements 

Each successive press of the 

 button selects a new range:

Imported active energy 

in kWh.

Exported active energy 

in kWh.

Imported reactive energy 

in kVArh.

Exported reactive energy 

in kVArh.

Total active energy in kWh.

Total reactive energy in 

kVArh.

 

Please note the register is  9999999.9 display over two lines.

4

 Set Up

4.1

 Set up Entry Methods

Some menu items, such as Password and CT, require a four-

digit number entry while others, such as supply system, require 

selection from a number of menu options.

4.1.1

 Menu Option Selection

1. Use the 

 and 

 buttons to scroll through the different 

options of the set up menu.

2. Hold the 

 button for 3 seconds to confirm your selection.

3. If an item flashes, then it can be adjusted by the 

 and 

 

buttons. 

4. Having selected an option from the current layer, hold the 

 

button for 3 seconds to confirm your selection.

5. Having completed a parameter setting, hold the 

ESC

U/I

 button for 

3 seconds to return to a higher menu level.

6. On completion of all setting-up, hold the 

ESC

U/I

 button for 3 

seconds, the measurement screen will then be restored.

4.1.2

 Number Entry Procedure

When setting up the unit, some screens require the entering 

of a number. In particular, on entry to the setting up section, a 

password must be entered. Digits are set individually, from left to 

right. The procedure is as follows:

1. The current digit to be set flashes and then can be adjusted using 

the 

 and 

 buttons.

2. Press the 

 button to more right to the next digit.

3. After setting the last digit, hold the 

 button for 3 seconds to 

save your selection.

4.2

 Communication

The RS485 port can be used for communication using Modbus RTU 

Protocol. To configure the Modbus settings, such as Address and 

Baud Rate, this is also done within the Password-protected set up 

menu. 

4.2.1

RS485 Address 

Use the 

 and 

 

buttons to select the menu 

option. The screen will show 

the current setting.

Hold the 

 button to set 

the meter Address.

Range: 001(default) to 247.

Hold the 

 button to 

confirm the selection.

Use the 

 and 

 buttons to choose the necessary number, 

then press the 

 button to move along to the next number. To 

save the new setting, hold the 

 button for 3 seconds until the 

selection stops flashing.

4.2.2

 Baud Rate

Use the 

 and 

 

buttons to select the menu 

option. The screen will show 

the current setting.

Hold the 

 button to 

enter the menu option, the 

current selection will flash.

Use the 

 and 

 

buttons to select the 

required option.

On completion of the entry procedure, hold the 

 button to 

confirm the setting.

4.2.3 

Parity

Use the 

 and 

 

buttons to select the menu 

option. The screen will show 

the current setting.

Hold the 

 button to 

enter the menu option, the 

current selection will flash.

Use the 

 and 

 

buttons to select the 

required option. 

Range: None (default), Odd 

or Even.

  
On completion of the entry procedure, hold the 

 button for 3 

seconds until the selection stops flashing.

4.2.4 

Stop bits

Use the 

 and 

 

buttons to select the menu 

option. The screen will show 

the current setting.

Hold the 

 button to 

enter the menu option, the 

current selection will flash.

Use the 

 and 

 

buttons to select the 

required option.

Range: 1 (default) or 2.

On completion of the entry procedure, hold the 

 button for 3 

seconds until the selection stops flashing.

4.5

 

CT Configuration

This unit is CT Operated, the primary (CT1) and secondary (CT2) of 

the current transformer need to be programmed correctly for the 

meter to scale the inputs accordingly.

%

%

%

Use the 

 and 

 

buttons to select the menu 

option. The screen will show 

the configure CT setting.

%

%

%

C1

Set the CT Ratio Value: 

Hold the 

 button to 

enter the CT Ratio setting 

screen. The range is from 

0001 to 9999. 0005A default

%

%

%

C2

o Switch from Circuit 1 (C1) 

to Circuit 2 (C2) press and 

hold the 

 button. Press 

and hold again to switch 

back to C1.

%

%

%

Secondary CT (CT2):

Hold the 

 button to set 

the CT secondary option: 

0.1A.(Not Configurable)

 
The CT Rate is the primary rate/ratio of the CT.
For Example: 200/100mA Current Transformers , so the CT Rate 
would be 0200 and the CT2 would be 0.1A.

4.6

 PT

The PT option sets the Secondary Voltage (PT2 100-500V) of the 
Voltage Transformer (PT) that may be connected to the meter. 

Use the 

 and 

 

buttons to select the menu 

option. The screen will show 

the current setting.The 

default value is 400V.

Secondary PT Setting:

Hold the 

 button to set 

the PT secondary option: 

100-500V.

Set the PT Ratio Value: 

Hold the 

 button to 

enter the PT Ratio setting 

screen. The range is from 

0001 to 9999.

 
The PT Rate is the PT Primary divided by the PT Secondary. For 
Example: Voltage Transformer - 11000÷110=100, so the PT Rate 
would be 0100 and the PT2 would be 110.

Summary of Contents for SDM630MCT-2L

Page 1: ... Phases Power Maximum Power Demand and Power Factor Imported Exported Total Active Energy Imported Exported Total Reactive Energy The unit has a Password Protected set up menu for Changing the Password System Configuration 1P2W 3P4W Demand Interval Time Reset for Demand Measurements 1 2 Current Transformer Primary Current This unit requires configuring to operate with the appropriate curren transf...

Page 2: ...l voltage THD Current THD for each phase 3 2FrequencyandPowerFactorandDemand Each successive press of the button selects a new range Frequency and Power Factor total Power Factor of each phase Maximum Power Demand Maximum Current Demand 3 3 Power Each successive press of the button select a new range Instantaneous Active Power in kW Instantaneous Reactive Power in kVAr Instantaneous Volt Amps in K...

Page 3: ...o the setting up section a password must be entered Digits are set individually from left to right The procedure is as follows 1 The current digit to be set flashes and then can be adjusted using the and buttons 2 Press the button to more right to the next digit 3 After setting the last digit hold the button for 3 seconds to save your selection 4 2 Communication The RS485 port can be used for comm...

Page 4: ...select the menu option The screen will show the configure CT setting C1 Set the CT Ratio Value Hold the button to enter the CT Ratio setting screen The range is from 0001 to 9999 0005A default C2 o Switch from Circuit 1 C1 to Circuit 2 C2 press and hold the button Press and hold again to switch back to C1 Secondary CT CT2 Hold the button to set the CT secondary option 0 1A Not Configurable The CT ...

Page 5: ...4 Wire 3P4W Use this section to set the type of electrical system Use the and buttons to select the menu option The screen will show the current setting Hold the button to enter the menu option the current selection will flash Use the and buttons to select the required option Hold the button to confirm your adjustment Hold the ESC U I button for 3 seconds to exit the set up menu 4 10 CLR The meter...

Page 6: ...ral not for 3P3W supplies Percentage Total Voltage Harmonic Distortion V THD between Phases 3 Phase supplies only Current THD for each Phase 5 1 2 Power factor and Frequency and Max Demand Frequency in Hz Instantaneous power Power 0 3600 MW Reactive power 0 3600 MVAr Volt amps 0 3600 MVA Maximum Demand Power since last reset Power factor Maximum Neutral Demand Current since the last reset for Thre...

Page 7: ...verse It cannot be configured from the set up menu 5 6 Reference Conditions of Influence Quantities Influence Quantities are variables that affect measurement errors to a minor degree Accuracy is verified under nominal value within the specified tolerance of these conditions Ambient temperature 23 C 1 C Input waveform 50 or 60Hz 2 Input waveform Sinusoidal distortion factor 0 005 Auxiliary supply ...

Page 8: ...e sequence of the meter Option1 Default Option 2 Requires phase sequence change L3 to L1 and L1 to L3 please refer to section 4 13 Option 3 Requires flow reversal please refer to section 4 12 Option 4 Requires phase sequence change L3 to L1 and L1 to L3 please refer to sectin 4 13 and CT reversal please refer to section 4 12 ...

Reviews: