background image

SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE

Operating instructions

Temperature differential controller

3 inputs, 1 output

709.75 | Z0 | 07.50 | Subject to change due to technical improvements!

EN

These operating instructions are part of the product.

Read these operating instructions carefully before use,
keep them over the entire lifetime of the product,
and pass them on to any future owner or user of this product.



Summary of Contents for tr 0301

Page 1: ...puts 1 output 709 75 Z0 07 50 Subject to change due to technical improvements EN Operating instructions These operating instructions are part of the product Read these operating instructions carefully...

Page 2: ...osing the casing 12 4 2 Mounting 13 4 3 Electrical connection 14 5 Display overview 18 6 Commissioning 19 7 Description of controller functions 20 7 1 Automatic storage tank charging 20 7 2 Maximum st...

Page 3: ...of the controller may only be performed by trained professional personnel Before commissioning the controller must be professionally assembled and installed by professional personnel in accordance wi...

Page 4: ...3 2 Danger levels in warning notices Danger level Likelihoodof occurrence Consequences resulting from non compliance DANGER Imminent threat of danger Death serious bodily injury WARNING Possible thre...

Page 5: ...ential controller called control ler in the following may only be used for controlling solar thermal systems within the permissible ambient conditions see chapter 12 2 2 Improper usage The controller...

Page 6: ...ns inappropriate power supply and connecting prohibited devices or faulty devices and incorrect assembly or installation Therefore all safety regulations apply when working on the mains supply Only el...

Page 7: ...4 Detecting faults Check the display regularly In case of faults isolate the cause see chapter 9 As soon as it becomes evident that safe operation is no longer possible e g visible damage remove the...

Page 8: ...on work improper operation and incorrect usage and maintenance Similarly we assume no responsibility for patent right or other right infringements of third parties caused by usage of this controller T...

Page 9: ...controller controls the solar thermal system 3 1 2 The structure of the solar circuit Temperature differential controller Storage tank Pump Temperature sensor 1 collector sensor Temperature sensor 2...

Page 10: ...re is a temperature difference of 8 K between the collector and the storage tank the pump is switched on The pump extracts the heat transfer fluid from the lower cooler area of the storage tank and pu...

Page 11: ...wn Display graphic display animated for controller operation and system settings Operating switch The following modes of operation can be selected On for commissioning and testing for function Automat...

Page 12: ...ng Only switch the power supply back on after the cas ing has been closed The upper casing is connected to the lower casing by two latches and fastened with a screw 4 1 1 Opening the casing Loosen the...

Page 13: ...ION Risk of injury and damage to the casing when drill ing Do not use the casing as a drilling template Choose a suitable installation site Drill the upper fastening hole Screw in the screw Remove the...

Page 14: ...ty supplier NOTE The device is to be connected to the grid by means of a plug with grounding contact or in the case of a fixed electrical installation via a disconnection device for complete disconnec...

Page 15: ...ing an appropriate tool Feeding the cable through the lower side of the casing diagram 2 WARNING Risk of electrical shock and fire due to cables com ing loose Fasten the flexible cabling to the casing...

Page 16: ...ints The polarity of the sensor contacts is not impor tant Do not lay sensor cables close to 230 volt or 400 volt cables minimum separation 100 mm If inductive effects are expected e g from heavy curr...

Page 17: ...e t a n k PE L1 N PE R1 N G r i d 2 3 0 V o p t i o n a l 1 1 5 V P u m p 2 3 0 V o p t i o n a l 1 1 5 V T e m p e r a t u r e s e n s o r 3 o p t i o n a l u p p e r a r e a o f s t o r a g e t a n...

Page 18: ...g the temperature unit C F 6 tube collector function 7 Setting the maximum storage tank temperature 8 Solar circuit symbols 9 Displays message Maximum storage tank temperature has been reached 10 Warn...

Page 19: ...nect the mains supply To switch on the pump set the operating switch to the upper position on The display is backlit in red onappears in the display After approx 3 sec onds on flashes in alternation w...

Page 20: ...rging The controller constantly compares the temperatures between the collector T1 and the lower area of the storage tank T2 As soon as the temperature in the collector T1 is 8 K constant fixed value...

Page 21: ...tor temperature During periods of high solar irradiance the tempera ture T1 of the heat transfer fluid can exceed 130 C The heat transfer fluid evaporates In this case the pump is stopped for protecti...

Page 22: ...extracted from the storage tank over an extended period of time holiday of intense solar irradiance A completely heated storage tank subjects the solar energy system to a higher thermal load and the s...

Page 23: ...gain CAUTION The solar energy system can freeze despite the acti vated anti freeze function During a power outage the anti freeze function does not operate During long term periods of frost due to res...

Page 24: ...re sensor T3 not included in delivery is also connected Use the buttons and to select temperature sensor T1 T2 T3 The selected temperature sensor and the current temperature reading appear in the disp...

Page 25: ...r in the hot water pipe and set to max 60 C The menu is open Press the SET button for approx 2 seconds until the storage tank maximum temperature flashes Change the storage tank maximum temperature us...

Page 26: ...no immersion sensors the sensor is outside the collector pipe The menu is open Press the button again until the symbol for T1 flashes Press the SET button for approx 2 seconds until the symbol for T1...

Page 27: ...i vated anti freeze function During a power outage the anti freeze function does not operate During long term periods of frost the system can freeze despite the anti freeze function If frost is expect...

Page 28: ...50 The menu is open Press the button until the anti freeze symbol flashes Press the SET button for approx 2 seconds until the small tick on the anti freeze symbol appears goes out 0Co C max max T1 D...

Page 29: ...ng description covers the most common problems encountered with the controller Only send in the controller with a precise fault description if none of the following faults are present 9 1 Fault causes...

Page 30: ...is burned out If necessary have professional personnel replace the fuse Replacement fuse is located in the casing The pump sym bol does not rotate The display is backlit in red OFF flashes Operating s...

Page 31: ...y are correctly con nected to the controller NOTE In case of a T3 short circuit the pump does not stop Interruption symbol and warning signal appear Secondary symptoms Possible cause remedy The pump s...

Page 32: ...following causes are possible The pump is faulty or not correctly connected The isolating valve in the solar circuit is still closed Air is in the solar circuit Since a standard circulation pump cann...

Page 33: ...e temperature is recorded by resistance sensors These are PT1000 temperature sensors Depending on the temperature the resistance value also changes A potentially defective sensor can be checked using...

Page 34: ...C 30 20 10 0 10 20 Resistance 882 922 961 1000 1039 1078 Temperature C 30 40 50 60 70 80 Resistance 1117 1155 1194 1232 1271 1309 Temperature C 90 100 110 120 130 140 Resistance 1347 1385 1423 1461 14...

Page 35: ...ER Risk of death by electrocution Remove the controller from the power supply before dismantling it To dismantle the controller follow the assembly instructions in the reverse order Dispose of the con...

Page 36: ...equipment faulty construction work unsuit able construction location or improper operation or use Legal guarantee claims shall only be accepted if notification of the fault is provided immediately af...

Page 37: ...Temperature differential controller Operational voltage 230 V 15 50 Hz optional 115 V 15 60 Hz Controller s own consumption 1 W Inputs 3 temperature recording Pt1000 Output 1 switched output switching...

Page 38: ...709752...

Reviews: