4
Technical
specifications
General
Dimension (mm): H: 256 x W: 193 x D: 78
Wall mounting (mm): c/c H: 160 x W: 125
Colour: Black
Installation kit included
Wire terminals
Wire cross-section: up to 16 mm
2
(single cable)/ up to
10 mm
2
(parallel connection)
Cable diameter: 8–22 mm
Terminal torque: 5 Nm
Cable strip length: 12 mm
Installation
Installation network: TN, IT or TT
Installation circuit breaker: Max 40 A (Easee Home) or
max 80 A (Easee Charge) overload protection. The short-
circuit current at the charging point (IkMax) must not
exceed 10 kA. If required by the installation, type-A earth
fault protection can be used for the circuit.
Protection
Degree of protection: IP44
Impact resistance: IK08
Fire class: UL94
Product overview
Installation kit
x5
x2
x3
x4
x2
x1
Blind cover
Protects the electrical
connections from
external influences.
Backplate
For attaching and
connecting to the
charging infrastructure.
Tool
Used for removing the
blind cover, after the
screw has been removed.