![Eagle Eye Power Solutions Vigilant ELM Series Troubleshooting Manual Download Page 3](http://html2.mh-extra.com/html/eagle-eye-power-solutions/vigilant-elm-series/vigilant-elm-series_troubleshooting-manual_4844534003.webp)
3.2 Clear Alarms from the Web-Interface
Calibrating the sensor(s) from the web-interface is the preferred option because multiple sensors
can be calibrated at once and there is less chance of user-error. These steps will assume you
understand how to login to the Vigilant.
1. Login to the web-interface and open the
Settings
section.
2. If using version 1.3.11 or later, click the
ELM Management
button.
3. If using an earlier version, type "elm/" after "settings/" in the URL bar.
4. On the ELM management page, click the link "Click here to see what other tasks are currently
scheduled."