Product Manual Rosa Thermostat
EAE KNX Rosa Thermostat
Rosa Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Page71 / 77
4.5.1 Parameter
Parameter
Setting
Description
Send Setpoint
Cyclic /
Cyclic and Change
Control values will be sent cyclically only or cyclical
and "Minimum Change" of heating control value is
reached.
Cyclic Sending Interval 10…
60
…65535 s
Time period to send heating control value over
“Heating Control Value” communication object.
Setpoint Button Step
Value
0.1K,
0.5K
, 1K
This parameter determines the step value of
Setpoint.
SETPOINT LIMITS
Maximum Setpoint
0...
40
...99 °C / °F
This parameter determines the maximum value of
Setpoint.
Minimum Setpoint
0
...99 °C / °F
This parameter determines the minimum value of
Setpoint.
Setpoint Range Limiting
(Mode based)
checked
/ unchecked
This parameter is limitting the Setpoint changes.
Allowed Range (+/-)
1...
5
...30 K
This parameter is shown when the "Setpoint Range
Limiting" is selected. Given value will be applied plus
and minus side of Setpoint.
For e.g. Limit is 5 and Comfort Setpoint 25 C. The
setpoint can decrease until 20 C, increase until 30 C.
HEATING & COOLING SETPOINTS
Multi Setpoint
Enable /
Disable
This parameter will be available If the Control Mode
Switchover is selected as
"Manual"
in Thermostat
Parameters Screen.
RETURN TO ETS PROGRAMMED VALUES
After Reset
Yes /
No
Setpoint values will be returned to last ETS
programmed values after device reset.
After Mode Change
Yes /
No
Setpoint values will be returned to last ETS
programmed values after any operating mode
change.
Reset on Site Object
Yes /
No
Setpoint values will be returned to last ETS
programmed values after Reset on Site Object is
enabled.
Reset on Site Value
0 /
1
/ Any Value
This parameter allows to reset device using by group
object.