4.6.4. Value Operation
Push button can be configured to send predefined values from different Data Types. Additionally, long, short
or double press actions can be selected for each Value transmitting individually. Up to 4 value can be sent
via one button.
4.6.4.1. Parameters
Parameter
Settings
Description
Value 1
None /
Short Press
/ Double Press / Triple /
Long Press (Start) / Long Press Repeat /
Long Press Release (Stop)
Value transmitting methods can be
selected.
Value 2
None
/ Short Press / Double Press / Triple /
Long Press (Start) / Long Press Repeat /
Long Press Release (Stop)
Value 3
Value 4
Data Type
1-bit
1-bit HVAC control mode
1-bit toggle
2-bit priority control
4-bit dimming control
4-bit blind control
1-byte unsigned
1-byte signed
1-byte HVAC opr. mode
1-byte percentage
1-byte counter/sequence
1-byte scene activate
1-byte scene learn
2-byte unsigned
2-byte signed
2-byte float
3-byte color
4-byte unsigned
4-byte signed
4-byte float
Data type can be selected individually
for each Value field.
Value
0
/1
Visible when “Data Type” selected as
“1 bit value”.
Cool
/ Heat
Visible when “Data Type” selected as
“1 bit HVAC C. Mode”.
00b No Priority, OFF
/ 01b No Priority, ON
10b Priority, OFF / 11b Priority, ON
Visible when “Data Type” selected as
“2 bit priority c
ontro
l”.
Decrease, Break
/ Decrease, 100 % … 1%
Increase, Break / Increase, 100% … 1%
Visible when “Data Type” selected as
“4 bit dimming c
ontro
l”.
Up, Break
/ Up, 100 % … 1%
Down,
Break / Down, 100% … 1%
Visible when “Data Type” selected as
“4 bit blind c
ontro
l”.
0
…255
Visible when Data Type is selected as
“1
-
byte unsigned”
-
128…
0
…127
Visible when Data Type is selected as
“1
-
byte signed”
Auto
/ Comfort / Standby / Economy /
Building Protection
Visible when Data Type is selected as
“1
-
byte HVAC operating mode”
0
…100 %
Visible when Data Type is selected as
“1
-
byte percentage”
0
…65535
Visible when Data Type is selected
as “2
-byte
unsigned”
–32768…
0
…32767
Visible when Data Type is selected
as “2
-
byte signed”
–671088…
0
…670760
Visible when Data Type is selected
as “2
-
byte float”
Parameter
Settings
Description