2. Communication Object Information 

2.1. Communication Object Table 

Overview of all communication objects of the device application can be seen on the following table. 

No 

Function 

Name 

DPT 

Length 

Flags 

In operation 

General 

1.002 

1 Bit 

CT 

Enable manual operation 

General 

1.003 

1 Bit 

CRW 

New devices addressing 

General 

1.003 

1 Bit 

CW 

Field capture 

General 

1.003 

1 Bit 

CW 

Request all statuses 

General 

1.003 

1 Bit 

CW 

Device status 

Feedback 

Non-DPT 

3 Bytes 

CWT 

Coded status switch 

Feedback 

Non-DPT 

2 Bytes 

CWT 

Coded status brightness value 

Feedback 

Non-DPT 

2 Bytes 

CWT 

Coded faults 

Feedback 

237.600 

2 Bytes 

CWT 

DALI line fault 

Feedback 

1.005 

1 Bit 

CRT 

10 

Mains connection fault 

Feedback 

1.005 

1 Bit 

CRT 

11 

Lamp fault 

Feedback 

1.005 

1 Bit 

CRT 

12 

Device fault 

Feedback 

1.005 

1 Bit 

CRT 

13 

Mains power failure status 

Feedback 

1.005 

1 Bit 

CRT 

14 

Scene 8-bit 

Scene 

17.001 

1 Byte 

CW 

15 

0=Scene 1, 1=Scene 2 

Scene 

1.022 

1 Bit 

CW 

16 

0=Scene 3, 1=Scene 4 

Scene 

1.022 

1 Bit 

CW 

17 

0=Scene 5, 1=Scene 6 

Scene 

1.022 

1 Bit 

CW 

18 

0=Scene 7, 1=Scene 8 

Scene 

1.022 

1 Bit 

CW 

19 

0=Scene 9, 1=Scene 10 

Scene 

1.022 

1 Bit 

CW 

20 

0=Scene 11, 1=Scene 12 

Scene 

1.022 

1 Bit 

CW 

21 

0=Scene 13, 1=Scene 14 

Scene 

1.022 

1 Bit 

CW 

22 

0=Scene 15, 1=Scene 16 

Scene 

1.022 

1 Bit 

CW 

23 

Broadcast Switch 

Broadcast 

1.001 

1 Bit 

CWU 

24 

Broadcast Set brightness value 

Broadcast 

5.001 

1 Byte 

CWU 

25 

Broadcast Relative dimming 

Broadcast 

3.007 

4 Bit 

CW 

26…215 

Switch 

Dali Device 1…64 

1.001 

1 Bit 

CWU 

Switch/Status 

CWTU 

Switch/Status 

CRWU 

Switch/Status 

CRWTU 

27…216 

Set brightness value 

Dali Device 1…64 

5.001 

1 Byte 

CWU 

Set brightness value/Status 

CWTU 

Set brightness value/Status 

CRWU 

Set brightness value/Status 

CRWTU 

28…217  Relative dimming 

Dali Device 1…64 

3.007 

4 Bit 

CW 

 

 

Summary of Contents for DA110

Page 1: ...Order Number 48107 EAE KNX DALI Gateway Product Manual DA110...

Page 2: ...ion 2 1 2 Technical Data 3 1 3 Connection Example 4 1 4 Operation and Display 4 2 Communication Object Information 5 2 1 Communication Object Table 5 2 2 Communication Object Descriptions 6 3 Paramete...

Page 3: ...atures are listed below Maximum 64 DALI devices e g electronic ballast transformer can be connected to DALI output DA110 enables to control 64 DALI devices individually and can store 16 different ligh...

Page 4: ...1 5 mm2 Max 300 m 0 75 mm2 Max 150 m 0 5 mm2 Max 100 m Installation 35mm mounting rail EN 60715 Operating elements Programming LED and button Green LED Yellow LED Red LED Manual button Test button Phy...

Page 5: ...fault is present Lamp fault ballast fault Fast Blink Initialization is active Manual LED 9 Lights up when manual control is activated by pressing manual button Manual Button 10 Activate Deactivate man...

Page 6: ...1 Lamp fault Feedback 1 005 1 Bit CRT 12 Device fault Feedback 1 005 1 Bit CRT 13 Mains power failure status Feedback 1 005 1 Bit CRT 14 Scene 8 bit Scene 17 001 1 Byte CW 15 0 Scene 1 1 Scene 2 Scene...

Page 7: ...manual operation can be read via this communication object Value of the object will be 1 after an ETS download if the Enable manual operation parameter in General tab is selected as enable Value will...

Page 8: ...if parameter is selected as after change Feedback will be sent on both occasions if the parameter is selected as after change or request Bit numbers and data which they represented is explained below...

Page 9: ...of whether a device or a group is selected Object will be activated if Enable Coded status switch object parameter in Feedback tab is selected as enable Feedback will be sent only after a request if...

Page 10: ...information of whether a device or a group is selected Object will be activated if Enable Coded status brightness value object parameter in Feedback tab is selected as enable Feedback will be sent onl...

Page 11: ...ill be activated if Enable Coded faults object parameter in Feedback tab is selected as enable Feedback will be sent only after a request if transmit mode parameter in Feedback tab is selected as afte...

Page 12: ...nly after a value change if parameter is selected as after change Feedback will be sent on both occasions if the parameter is selected as after change or request value 0 gateway supply works properly...

Page 13: ...mains connected to DALI line NOTE Overvoltage sense circuitry on the DALI line is triggered on voltages above 40V So any voltage above 40V is considered as mains 14 Scene 8 bit Scene 17 001 1 byte CW...

Page 14: ...ballasts 25 Broadcast Relative dimming Broadcast 3 007 4 bit CW This object is used to dim all connected DALI ballast The brightness value is changed in the defined direction with the parameterized sp...

Page 15: ...ed to switch DALI device 1 64 ON or OFF 44 Group 1 Brightness value Dali Device 1 64 5 001 1 byte CWU Set brightness value Status after change CWTU Set brightness value Status after request CRWU Set b...

Page 16: ...elected enable following parameters come up In operation value true false Telegram value can be selected as 1 or 0 Operation send interval sec 1 300 65535 Telegram value is sent cyclically according t...

Page 17: ...e dimming commands separately If these parameters are selected no then it is not possible to switch on or off the lighting fixtures via brightness value 1 byte or relative dimming 4 bit objects of the...

Page 18: ...y device that has a fault lamp is present or not Enable Device fault object enable disable Parameter enables Fault ballast object This object is used for reporting whether there is any offline or malf...

Page 19: ...applied to the mains line of DA110 device Transmit mode description is the same for all parameters in Feedback tab But selections can be made independently for each parameter Transmit mode after reque...

Page 20: ...change Parameter defines the brightness value of ballasts on DALI line voltage loss Lamp values on DALI voltage recovery 0 0 100 255 no change Parameter defines the brightness value of ballasts on DA...

Page 21: ...us of the group can be read from this object itself or separate status object No response option disables the Read flag of object After request mode status object only response to a read request After...

Page 22: ...ct as well Activate scenes 1 16 no yes Scene count can be selected in this page This page only activates the DALI device control objects Unselected device adresses can still be controlled in scenes Al...

Reviews: