Product Manual DA110
EAE KNX DALI Gateway
DA110 R
3
.0
©
EAE Technology
www.eaetechnology.com
Page 3 / 21
1.2. Technical Data
Type of protection
IP 20
EN 60529
Safety class
II
EN 61140
KNX supply
(4)
Voltage
Current consumption
21 - 30V DC, SELV
< 10mA
Mains supply
(6)
Voltage
Power consumption
Current consumption
85 - 300V AC @ 50-60Hz
Max. 8W
100mA @ 85V AC
DALI supply
(5)
Voltage
Current
16V DC typical
Max.
1
20mA
Connections
Screw terminals
Max tightening torque
KNX terminal
0,05 - 2,5mm² solid wire
0,03 - 1,5mm² stranded wire
0.5Nm
Red - grey bus connect terminal
Output
Number of DALI devices
Cable lengths
Max. 64
1.5 mm
2
Max.
300 m
0.75 mm
2
Max. 150 m
0.5 mm
2
Max. 100 m
Installation
35mm mounting rail
EN 60715
Operating elements
Programming LED and button
Green LED
Yellow LED
Red LED
Manual button
Test button
Physical address localization
Power OK
Initialization active (fast blink)
A DALI device fault present (slow blink)
DALI line power failure (constant on)
No Mains connection (constant on)
Manual operation active
Activate the manual control over test button
Switch-dim DALI output (when Manual Mode is active)
Temperature range
Ambient
Storage
-5°C +45°C
-25°C +55°C
Humidity
Max. air humidity
95% no moisture condensation
Dimensions
Width W in mm
Width W in units
70 x W x 91mm
69mm
4 modules (18mm modules)
Box
Plastic, polycarbonate, colour grey
CE
In accordance with the EMC guideline and low voltage directives.