EAE DA110 Product Manual Download Page 18

Product Manual DA110 

EAE KNX DALI Gateway 

  

       

DA110 R2.0 

©

EAE Technology  

 

 

www.eaetechnology.com  

 

 

Page 17 / 21 

3.2. Feedback 

 

Enable “DALI line fault” object 

  

enable 

*

disable

 

Parameter enables “Fault gateway supply” object. This object is used for reporting DALI gateway supply fault. 

Possible causes of the fault are no mains connection to gateway supply terminal, power supply malfunction 

or short circuiting DALI line more than 100ms. Please check 

2.2 Communication Object Descriptions

  for 

detailed object information.

 

 

Enable “Mains connection fault” object 

  

enable 

*

disable

 

Parameter enables “Fault mains connected” object. This object is used for reporting a misconnection of mains 

to the DALI line.

 

 

Enable “Lamp fault” object 

   

enable 

 *disable

 

Parameter enables “Fault lamp” object. This object is used for reporting whether there is any device that has 
a fault lamp is present or not.

 

 

Enable “Device fault” object 

   

enable 

 *disable

 

Parameter enables “Fault ballast” object. This object is used for reporting whether there is any offline or 
malfunctioned ballast/driver is present or not.

 

 

Enable “Device status” object 

   

enable 

 *disable

 

Parameter enables “Device status” object. This communication object is used for getting all current faults and 
states of a DALI device in one comprehensive telegram.

 

 

Enable “Coded status switch” object 

   

enable 

 *disable

 

Parameter enables “Coded status switch” object. This object is used to get switch status of a DALI group or an 
individual DALI ballast/driver.

 

 

Enable “Coded status brightness value” object 

   

enable 

 *disable

 

Parameter enables “Coded status brightness” object. This object is used to get brightness value of a DALI 
group or an individual DALI ballast/driver.

 

 

Enable “Coded faults” object 

   

enable 

 *disable

 

Parameter enables “Coded faults” object. This object is used to get fault data of a DALI group or an individual 
DALI device.

 

 
 

Summary of Contents for DA110

Page 1: ...Order Number 48107 EAE KNX DALI Gateway Product Manual DA110...

Page 2: ...ion 2 1 2 Technical Data 3 1 3 Connection Example 4 1 4 Operation and Display 4 2 Communication Object Information 5 2 1 Communication Object Table 5 2 2 Communication Object Descriptions 6 3 Paramete...

Page 3: ...atures are listed below Maximum 64 DALI devices e g electronic ballast transformer can be connected to DALI output DA110 enables to control 64 DALI devices individually and can store 16 different ligh...

Page 4: ...1 5 mm2 Max 300 m 0 75 mm2 Max 150 m 0 5 mm2 Max 100 m Installation 35mm mounting rail EN 60715 Operating elements Programming LED and button Green LED Yellow LED Red LED Manual button Test button Phy...

Page 5: ...fault is present Lamp fault ballast fault Fast Blink Initialization is active Manual LED 9 Lights up when manual control is activated by pressing manual button Manual Button 10 Activate Deactivate man...

Page 6: ...1 Lamp fault Feedback 1 005 1 Bit CRT 12 Device fault Feedback 1 005 1 Bit CRT 13 Mains power failure status Feedback 1 005 1 Bit CRT 14 Scene 8 bit Scene 17 001 1 Byte CW 15 0 Scene 1 1 Scene 2 Scene...

Page 7: ...manual operation can be read via this communication object Value of the object will be 1 after an ETS download if the Enable manual operation parameter in General tab is selected as enable Value will...

Page 8: ...if parameter is selected as after change Feedback will be sent on both occasions if the parameter is selected as after change or request Bit numbers and data which they represented is explained below...

Page 9: ...of whether a device or a group is selected Object will be activated if Enable Coded status switch object parameter in Feedback tab is selected as enable Feedback will be sent only after a request if...

Page 10: ...information of whether a device or a group is selected Object will be activated if Enable Coded status brightness value object parameter in Feedback tab is selected as enable Feedback will be sent onl...

Page 11: ...ill be activated if Enable Coded faults object parameter in Feedback tab is selected as enable Feedback will be sent only after a request if transmit mode parameter in Feedback tab is selected as afte...

Page 12: ...nly after a value change if parameter is selected as after change Feedback will be sent on both occasions if the parameter is selected as after change or request value 0 gateway supply works properly...

Page 13: ...mains connected to DALI line NOTE Overvoltage sense circuitry on the DALI line is triggered on voltages above 40V So any voltage above 40V is considered as mains 14 Scene 8 bit Scene 17 001 1 byte CW...

Page 14: ...ballasts 25 Broadcast Relative dimming Broadcast 3 007 4 bit CW This object is used to dim all connected DALI ballast The brightness value is changed in the defined direction with the parameterized sp...

Page 15: ...ed to switch DALI device 1 64 ON or OFF 44 Group 1 Brightness value Dali Device 1 64 5 001 1 byte CWU Set brightness value Status after change CWTU Set brightness value Status after request CRWU Set b...

Page 16: ...elected enable following parameters come up In operation value true false Telegram value can be selected as 1 or 0 Operation send interval sec 1 300 65535 Telegram value is sent cyclically according t...

Page 17: ...e dimming commands separately If these parameters are selected no then it is not possible to switch on or off the lighting fixtures via brightness value 1 byte or relative dimming 4 bit objects of the...

Page 18: ...y device that has a fault lamp is present or not Enable Device fault object enable disable Parameter enables Fault ballast object This object is used for reporting whether there is any offline or malf...

Page 19: ...applied to the mains line of DA110 device Transmit mode description is the same for all parameters in Feedback tab But selections can be made independently for each parameter Transmit mode after reque...

Page 20: ...change Parameter defines the brightness value of ballasts on DALI line voltage loss Lamp values on DALI voltage recovery 0 0 100 255 no change Parameter defines the brightness value of ballasts on DA...

Page 21: ...us of the group can be read from this object itself or separate status object No response option disables the Read flag of object After request mode status object only response to a read request After...

Page 22: ...ct as well Activate scenes 1 16 no yes Scene count can be selected in this page This page only activates the DALI device control objects Unselected device adresses can still be controlled in scenes Al...

Reviews: