EA Technology
UltraTEV Monitor
TM
Operating Manual
2178L014
82
17.3
Wall Mount Hub and Power Supply
17.3.1
Hub Unit Controls
The Wall Mount Hub is supplied with NO user interface controls. However the instrument maybe
controlled locally using either, a wired or wireless connection via a Laptop or Tablet PC.
Alternatively, access to the Hub may be gained through a remote desktop connection.
Reset button:
Micro-switch accessed by hole in the enclosure
17.3.2
Power Supply Controls
The Power Supply has NO user interface controls. To switch the power on and off use a mains outlet
with a switch.
17.3.3
Power Supply Input
Voltage:
110-230V AC (nominal)
Frequency:
50-60 Hz (nominal)
Maximum Power:
350W
Fusing
:
2x Anti-surge (T) 5A Double Pole Fusing
Minimum 1000A Breaking Capacity
1x Fast (F) 100mA
17.3.4
Power Supply Output
Hub Unit Power:
12V DC, Maximum 5A
Node Power:
48V DC, Maximum 5.2A
Phase Reference:
9V AC, Maximum 100mA, Short-circuit Protected
Fusing:
1x
Anti-surge (T) 7A Fuse
1x Anti-surge (T) 8A Fuse
NOTE:
All fuses are 5 x 20 mm cartridge type
17.3.5
Optional 48V Power Supply Input
Voltage In:
48V DC
Phase Reference Frequency:
50-60 Hz (nominal)
Maximum Power:
350W
Fusing :
1x
Anti-surge (T) 5A Fuse
17.3.6
Optional 48V Power Supply Output
Hub Unit Power:
12V DC, Maximum 5A
Node Power:
48V DC, Maximum 5.2A
Phase Reference:
9V AC, Maximum 100mA
Fusing:
1x
Anti-surge (T) 7A Fuse
1x Anti-surge (T) 8A Fuse
NOTE:
All fuses are 5 x 20 mm cartridge type
17.3.7
Hub Unit Indicators
System Power:
1x
Green LED
UltraBus Power:
1x
Green LED
Monitor Health:
1x
Green LED
Alarm, SCADA Outputs 1-3:
4x
Red LED
Summary of Contents for UltraTEV Monitor
Page 1: ......
Page 2: ......
Page 3: ...UltraTEV Monitor Operating Manual Product Code UTM2 Version 4 October 2016...
Page 4: ...EA Technology UltraTEV MonitorTM Operating Manual 2178L014 1...
Page 78: ...EA Technology UltraTEV MonitorTM Operating Manual 2178L014 75...
Page 95: ...EA Technology UltraTEV MonitorTM Operating Manual 2178L014 92 27 Notes...
Page 112: ......