Figure 53: Viewing a graph of selected data
14.1
Measurement Types
Each of the UltraTEV Monitor
™
channels collects a variety of different measurements and these are
recorded in the summary table. The following table explains what each of these different
measurement types is.
Maximum
Level
This is the maximum of the Maximum Amplitude (dB for TEV, pC for Cable
PD) of samples.
Average Level
This is the average of the Mean Amplitude (dB for TEV, pC for Cable PD) of
samples.
Maximum PPC This is the maximum of the Maximum Pulses Per Cycle of samples.
Average PPC
This is the average of the Mean Pulses Per Cycle of samples.
Total 1
st
Count This is the total of the First Counts of the samples.
% Total Events This is the Total First Count for the channel divided by the Total number of
pulses detected by the system. Note that the total number of pulses detected
by the system is the sum of TEV or Cable PD event count of the samples.
% 1
st
Count
This is the percentage of the total number of pulses that this channel
detected first.
Maximum STS
This is the maximum of the Maximum Short Term Severity of samples.
Average
Overall
Severity
This is the average of the Overall Severity of the samples.
Summary of Contents for UltraTEV Monitor
Page 1: ......
Page 2: ......
Page 3: ...UltraTEV Monitor Operating Manual Product Code UTM2 Version 4 October 2016...
Page 4: ...EA Technology UltraTEV MonitorTM Operating Manual 2178L014 1...
Page 78: ...EA Technology UltraTEV MonitorTM Operating Manual 2178L014 75...
Page 95: ...EA Technology UltraTEV MonitorTM Operating Manual 2178L014 92 27 Notes...
Page 112: ......