INSTRUCTION MANUAL (ATEX / IECEx / UKEx)
GNExS2FDC024-S & GNExS2HDC024-S
Alarm Horn Sounder
–
SIL2
For use in Flammable Gas Atmospheres
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D157-00-671-IS
Issue 2
06-03-2023
Sheet 1 of 14
GNExS2FDC024-S
GNExS2HDC024-S
1) Product Table
Model Number
Nominal
Input Voltage
Voltage Range
Nominal
Input Current
Max.
Current
Sound
Pressure Level
P2, dB(A)
Sound
Pressure Level
P3, dB(A)
P2
P3
P2
P3
Max*
Nom
.†
Max*
Nom
.†
GNExS2FDC024-S
24Vdc
20-28Vdc
324mA
740mA
324mA
740mA
120
115
123
118
GNExS2HDC024-S
24Vdc
20-28Vdc
324mA
740mA
324mA
740mA
124
119
127
122
*Max = Tone 4
†
Nom. = Tone 44
The table shows the input current taken by the various sounders.
The current levels shown above are for the 440Hz Continuous tone @ nominal input voltage at P2 and P3 power setting.
Nominal current at nominal voltage.
Max rated current at worst case supply voltage.
Table 1: Electrical Ratings.
Ensure the system power supply is capable of providing the maximum current required for all sounders. Review associated cable size,
length and quantity of sounders on each circuit.