INSTRUCTION MANUAL
GNExCP7-BG-S, GNExCP7-BG-D
Call Point
Class I & II Div 2 ; UL60947
NEC / CEC / ATEX / IECEx / UKEx Zone 1, 2, 21, 22
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D202-00-011-IS
Issue 3 25-08-2023 Sheet 1 of 8
GNExCP7-BG
1) Product
Table
Unit Type Code
Input Voltage
Input Current
GNExCP7-BG-S
GNExCP7-BG-D
250Vac Max
5.0A Max ATEX/IECEx/UKEx
3.33A Max Class Div/Zone
GNExCP7-BG-S
GNExCP7-BG-S-L
GNExCP7-BG-D
GNExCP7-BG-D-L
48Vdc Max
1.0A Max
24Vdc Max
3.0 Max
GNExCP7-BG-S-C
GNExCP7-BG-D-C
48Vdc Max
20mA Max
Table 1: Electrical Ratings
2) Warnings
WARNINGS:
USE COVER BOLTS CLASS A4-70
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT
POTENTIAL ELECTROSTATIC CHARGING HAZARD – SEE INSTRUCTIONS
FOR INDOOR OR OUTDOOR USE
TO REDUCE THE RISK OF IGNITION OF HAZARDOUS ATMOSPHERES, CONDUIT RUNS
MUST HAVE A SEALING FITTING CONNECTED WITHIN 2 INCHES OF ENCLOSURE
AVERTISSEMENT:
UTILISER COUVRIR BOULONS CLASSE A4-70
NE PAS OUVRIR UN PRESENCE D'ATMOSPHERE EXPLOSIVE
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - VOIR LES INSTRUCTIONS
POUR USAGE INTÉRIEUR OU EXTÉRIEUR
POUR RÉDUIRE LE RISQUE D'INFLAMMATION DES ATMOSPHÈRES DANGEREUSES, LES CONDUITES DE CONDUIT
DOIVENT AVOIR UN RACCORD D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 2 POUCES DE ENCLOS