E2S GNExB2LD2AC115 Instruction Manual Download Page 1

INSTRUCTION MANUAL 

STExB2LD2 

Flameproof LED Beacons

 

For use in Flammable Gas and Dust Atmospheres

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D199-00-401-IS

 

Issue 4

 

04-01-21

 

 

Sheet 1 of 6

 

 

 
 

 

 

STExB2LD2

 

 

 

 

1)  Product Table 

 

Standard 

Model 

Nom. Voltage 

Voltage Range 

Nom. Operating 

Current* 

Max Current 

ATEX / 

IECEx / 

NEC / 

CEC 

GNExB2LD2DC024 

24Vdc 

18-54Vdc

1

 

18-30Vdc

2

 

230mA 

500mA 

GNExB2LD2AC115 

115Vac 

110-120Vac 50/60Hz 

95mA 

180mA 

GNExB2LD2AC230 

230Vac 

220-240Vac 50/60Hz 

50mA 

100mA 

*Rate at 1Hz 

1

ATEX / IECEx Conformity 

2

NEC / CEC Conformity 

 
The table shows the input current taken by the various beacons. 
A supply voltage variation of +/-10% outside the voltage range is permissible. 
Nominal current at nominal voltage and 1Hz flash rate. 
Max. rated current at worst case supply voltage and flash rate. 

Table 1: Electrical Ratings 

 
Ensure the system power supply is capable of providing the maximum current required for all beacons. Review associated cable size, 
length and quantity of beacons on each circuit. 
 
 
 

 

2) 

Warnings

  

 

 

 

  POTENTIAL ELECTROSTATIC CHARGING HAZARD. 

  DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS 

PRESENT. 

  ALL ENTRIES M20 X 1.5MM. 

  USE  SUITABLE  RATED  CABLES  AND  CABLE  GLANDS 

IF  TEMPERATURE  EXCEEDS  AS  PER  STANDARDS 
INDICATIONS BELOW. 
FOR ATEX / IECEx STANDARDS: 

70ºC AT ENTRY OR 80ºC AT BRANCHING POINT. 

FOR NEC / CEC STANDARDS: 

60ºC AT ENTRY OR 60ºC AT BRANCHING POINT. 
 

3)  Rating & Marking Information 

 
All  units  have  a  rating  label,  which  carries  the  following 
important information: 
 

  Unit Model. 

  Voltage Range 

  Nominal Voltage 

  Max. Current 

 
See Table 1 for electrical ratings of each Unit Model. 
 
 
 
 
 
 
 
 
 

Summary of Contents for GNExB2LD2AC115

Page 1: ...range is permissible Nominal current at nominal voltage and 1Hz flash rate Max rated current at worst case supply voltage and flash rate Table 1 Electrical Ratings Ensure the system power supply is c...

Page 2: ...res Part 0 Equipment General Requirements CAN CSA C22 2 No 60079 1 Ed 3 2016 Electrical Apparatus for Explosive Gas Atmospheres Part 1 Flameproof Enclosures d Ratings STExB2 LD2DC024 LD2AC115 LD2AC230...

Page 3: ...y should only be fixed to services that can carry the weight of the unit STExB2X21 models shall not be mounted with the lamp down The STEx beacons should be securely bolted to a flat surface using 9 0...

Page 4: ...14 Wire insulation needs to be stripped 8mm Wires may be fitted securely with crimped ferrules Figure 4 Wire Preparation Terminal screws need to be tightened down with a tightening torque of 0 45 Nm...

Page 5: ...in no case more than the size of the conduit or 50mm whichever is the lesser 8 Flash Pattern Settings The GNExB2 beacon can produce different flash patterns as shown in Table 2 The flash patterns are...

Page 6: ...and casting To reattach the lens the fixings MUST be in the order shown in figure 9 Figure 9 Lens Guard Fixings Order 11 Maintenance Overhaul and Repair Maintenance repair and overhaul of the equipme...

Page 7: ...L DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D...

Page 8: ...Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 Gb II 2D Ex tb IIIC T...

Page 9: ...e and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...