E2S E2xL15EG Instructions/Service Manual Download Page 1

 

__________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)20 8743 8880 

                                                                                                                                                             

www.e2s.com             Fax: +44 (0)20 8740 4200 

Document No. IS4212     Issue: B                           09-03-06               Sheet 1 of 2 

INSTRUCTION & SERVICE MANUAL 

E2xL15EG LOUDSPEAKERS 

For Use In Hazardous Areas 

 
 
 
 

 

15 Watt Loudspeaker 

 

70V or 100V Line Transformer 
with 15W, 7.5W, 3W and 1W tapings 

 

8 ohm or 16 ohm 

 

Operating Temperature Range 
-20ºC to +55ºC 

 

Unit Type No.

 

E2xL15EG 

 

Impedance:

 

8 ohm or 16 ohm  

 

 

70V Line or 100V Line

 

II 3G   EEx nA II T4 (Tamb. -20ºC to +55°C)

 

Certificate No. 

    DEMKO 06 ATEX 0421554 

 

Group/Category:    

II

 

3G 

 

Zone:

   

   Zone 2 

 
PRE-INSTALLATION 

The E2xL15EG loudspeakers must be installed in 
accordance with the relevant parts of the EN60079 standards 
or the equivalent IEC standards.

 

Flat Washer

Spring Washer

M4 Hex
Socket Screw

 

 
WARNING – DO NOT OPEN WHEN ENERGISED

 

 
MOUNTING

 

The  E2xL15EG  loudspeaker  must  be  mounted  using  the 
rotating bracket as shown.  

 

Release screw to rotate 
bracket.

18° Increments

 

 

 

 
 
 
WARNING – TO AVOID A POSSIBLE ELECTROSTATIC 
 

       CHARGE ONLY CLEAN THE UNIT WITH A 

 

       DAMP CLOTH 

 
 
E2xL15EG Loudspeaker 70V and 100V PCB Layout 
 

 

 

 
E2xL15EG Loudspeaker 8 ohm and 16 ohm PCB Layout 

 

 

 
 
WIRING 

The E2xL15EG loudspeaker has two M20 cable entries one of 
which is fitted with an M20 blanking plug. This should be 
removed if two cable entries are required. Cable entry devices 
shall be used which ensure a minimum ingress protection of 
IP54. 
 
 The cable connections are made to the terminal blocks on the 
pcb assembly in the enclosure. 

 

 
WARNING - ALL ELECTRICAL WIRING MUST BE 

INSTALLED IN ACCORDANCE WITH THE 
RELEVANT STANDARDS AND ANY LOCAL 
CODES THAT MAY APPLY 

 
 
 
 

Reviews: