E2S BExDL15D Instruction Manual Download Page 1

 

 

__________________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 

Document No. IS 2453-P      Issue E     12-03-10                                       Sheet 1 of 4 

 

INSTRUCTION MANUAL (ATEX / IECEx) 

BExDL25D and BExDL15D 

Flameproof Loudspeakers

 

For use in Flammable Gas and Dust Atmospheres

 

 

 
 
 
 
 
 
1) Introduction 

 
The  BExDL25D and  BExDL15D  are flameproof  loudspeakers 

which  are certified to the meet the requirements of the ATEX 
directive 94/9/EC  and IECEx scheme.  The  loudspeakers  can 

be used  in hazardous  areas where  potentially flammable  gas 
and  dust  atmospheres  may  be  present.  There  are  four 

versions of each  loudspeaker,  8 ohm or 16 ohm  and  70V or 
100V  Line  transformer.  On  70V  and  100V  line  transformer 
units  there  are  four  output  tappings  for  each  size  of 

loudspeaker. The BExDL25D unit produces output levels in the 
117dB(A)  range  and  the  BExDL15D  unit  produces  output 

levels in the 112dB(A) range. Both loudspeakers can be used 
in Zone 1 and Zone 2 areas with gases in groups IIA, IIB and 
IIC and temperature Classifications of T1, T2, T3 and T4. For 
ambient temperatures over +55ºC the gas groups are limited to 
IIA and IIB.  They can also be used in Zone 21 and Zone 22 

areas for combustible dusts and have an IP rating of IP 67 and 
a  surface  temperature  rating  of  T100ºC  up  to  +55ºC  and 

T115ºC over +55ºC.  
 

2)  

Marking

 

 
All  units  have  a  rating  label,  which  carries  the  following 

important information:- 
 
Unit Type No.     

BExDL25D   or   BExDL15D

 

 
Impedance:        8 ohm or 16 ohm   

            70V Line or 100V Line 

 
Codes:   

Ex d IIC T4 for T

a

 –50°C to +55

°

Ex d IIB T4 for T

a

 –50°C to +70

°

       Ex tD A21 IP67 T115°C based on max Ta of +70°C 

 

Certificate No’s

    KEMA 99ATEX6312 

 

 

IECEx KEM 10.0003

 

 

        

 

 

 

 

“Warnings”

 

    

DO NOT OPEN WHEN AN EXPLOSIVE  

                               GAS OR DUST ATMOSPHERE IS PRESENT 

 

      COVER BOLTS CLASS A4-80 

 

     

USE HEAT RESISTING CABLES AND CABLE GLANDS 

 

       (Rated 110ºC) AT AMB. TEMPERATURES OVER 40ºC 

 
Year of Construction /  
Serial No.      

 

 i.e.   10 / 1DL23000001 

 

 
 
 

 
 

 

 
 
 

3) 

Type Approval Standards

 

 

The  loudspeakers  have  EC  Type  Examination  and  IECEx 
certificates issued  by  KEMA and have  been  approved to  the 

following standards:- 
 

EN60079-0:2006   IEC60079-0:2004 (Ed4)

      

General Requirements

 

EN60079-1:2007   IEC60079-1:2007

 

(Ed6)

        Flameproof Enclosure ‘d’ 

 

EN61241-0:2006   IEC61241-0:2004 (Ed1)       Dust General 

          Requirements 

EN61241-1:2004   IEC60079-1:2004 (Ed1)       Dust Enclosures tD 

 

4) 

Installation Requirements

 

 
The  loudspeakers  must  be  installed  in  accordance  with  the 
latest  issues  of  the  relevant  parts  of  the  BS  EN  60079 
specifications or the equivalent IEC specifications – Selection, 
Installation and maintenance of electrical apparatus for use in 
potentially  explosive  atmospheres  (other  than  mining 

applications or explosive processing and manufacture):- 
 

EN60079-14:2008

    

Electrical Installations in Hazardous 

IEC60079-14:2007 (Ed4) 

Areas (other than mines)

 

 

EN60079-10:2003

   

Classification of Hazardous Areas

 

IEC60079-10:2008 (Ed1) 

 
The  installation of  the  units  must also  be in  accordance  with 
any local codes that may apply and should only be carried out 
by a competent electrical engineer who has had the necessary 
training. 

 

5) 

Zones,  Gas  Group,  Category,  IP  Rating  and 
Temperature Classification 

 

The BExDL25D and BExDL15D loudspeakers have been have 
been certified Ex d IIC T4 for Ta –50°C to +55ºC and Ex d IIB 
T4 for Ta –50°C to +70ºC for gas and Ex tD A21 IP67 T115ºC 
based on max. Ta of +70ºC for dust. This means that the units 

can be installed in locations with the following conditions:- 
 

Area Classification Gas: 

 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 

normal operation. 

Zone 2 

Explosive  gas  air  mixture  not  likely  to  occur, 
and if it does, it will only exist for a short time. 

  

Gas Groupings: 

 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC (Up to +55ºC only)  Hydrogen and Acetylene 

 

0518 

II 2G/D 

CE Marking: 
Notified Body No. 

 

Reviews: