E2S Appello A121APPX Instruction Manual Download Page 1

                                        

INSTRUCTION MANUAL 

A121APPX,  AL121APPX & MV121 APPELLO  

Alarm Tone and Voice Annunciation Sounder 

 

European Safety Systems Ltd.

  

Impress House, Mansell Road, Acton, London W3 7QH    

 

 

[email protected]

     Tel: +44 (0)208 743 8880 

                                                                                                                                                        

www.e2s.com

    Fax: +44 (0)208 740 4200 

Document No. D166-00-001-IS_Issue_2    01-05-12 
 

Sheet 1 of 10 

1)  Introduction 

The  Appello  tone  and  speech  annunciation 
sounder has three different styles in AC and DC. 

·

 

A121APPX & MV121     Sounder 

·

 

AL121APPX   Sounder-Beacon Combination 
Sounder-Beacon  Combination  units  are 
available  as  either  a  high  output  LED  or 
Xenon strobe. 
 

These  Sounder  units  share  a  common  set  of 
functions:- 

·

 

4  stages,  each  stage  can  record  up  to  30 
seconds of CD quality audio. 

·

 

Facility to record via an on board microphone 
or a line in input. 

·

 

The  recorded  message  can  be  played  back 
proceeded  either  with  or  without  the  choice 
of one of forty five tones. 
 

The Beacon functions are either:- 

·

 

Xenon Strobe - 1Hz flash rate 

·

 

LED - Either Steady or 2Hz blink rate 

2)  Operating and Marking 

 
All 

units 

have 

the 

following 

operating 

requirements and limitations. 
 
Unit Type No.     Voltage    Range          Current 
Sounder only outputs 
A121APPX DC   24Vdc    14-30Vdc      1.51A  
& MV121 DC 
 

 

Max Current 1.85A @ 30Vdc 

A121APPX AC  115Vac   90-260Vac   542mA 
&  MV121 AC 

230Vac   90-260Vac   517mA 

 

 

Max Current 668mA @ 90Vac 

 
AL121APPX combined unit - Add selected 
sounder & beacon currents to calculate total 
current required. 
  
 

 

Beacon only outputs 

LED Beacon DC   24Vdc    10-30Vdc      157mA 
 

 

Max Current 166mA @ 30Vdc 

LED Beacon AC  115Vac   90-260Vac   60mA 
 

 

230Vac   90-260Vac   35mA 

 

 

Max Current 60mA @ 90Vac 

 
Xenon Beacon DC 12Vdc   10-14Vdc      500mA 
 

 

  24Vdc   20-28Vdc      250mA 

Xenon Beacon AC /-10%Vac   100mA 
 

 

 230Vac  +/-10%Vac    50mA 

 
Operating Temp:  -20 to +55

°

All units IP Rating: Type 4 / 4X / 3R / 13 , IP66 
MV121    

additional IP Rating: IP67 

 

Marking:  

 

 
 

3)  Installation & Wiring Requirements

 

 
A121APPX 

 

 
 
AL121APPX 

 

 
 
MV121 

 

 
 
 

AUTHORIZED DISTRIBUTOR | ControlSystemsUSA.com | Houston, Texas USA | [email protected] | 832-615-3588

Summary of Contents for Appello A121APPX

Page 1: ...es The Beacon functions are either Xenon Strobe 1Hz flash rate LED Either Steady or 2Hz blink rate 2 Operating and Marking All units have the following operating requirements and limitations Unit Type...

Page 2: ...move header for steady mode Keep header in standard position for 2Hz flashing mode 5 Unit Set up and Recording The unit will need to be configured to suit the end user If recording either via the onbo...

Page 3: ...e to the second third or fourth stage tone link the ve supply line to terminal relevant stage terminal Ie for Stage 2 link the ve supply to the S2 terminal for Stage 3 link the ve supply to the S3 ter...

Page 4: ...The following guide is designed to get the user quickly interfacing with the Appello unit The Appello unit can be set up to either play an attention seeking tone and then a recorded message or just pl...

Page 5: ...tage 3 Switch 2 Off Switch 3 Off Alarm Stage 4 3 Stage selection switch 4 Line In selected On board Microphone selected 5 Program Record Erase Mode ON Playback Record Erase Mode OFF 6 Message Tone Pla...

Page 6: ...3 Set Switch S2 positions 2 4 to ON For Stage 4 Set Switch S2 position 4 to ON To record from Line in instead of the on board microphone follow above step 1 but set Switch S2 position 4 to OFF 2 Swit...

Page 7: ...01 05 12 Sheet 7 of 10 Quick Ref Erase Single stage Mode Stage 1 illustrated 1 For Stage 1 Set Switch S2 positions 2 3 7 to ON Alternatively for For Stage 2 Set Switch S2 positions 3 7 to ON For Stag...

Page 8: ...40 4200 Document No D165 00 001 IS_Issue_2 01 05 12 Sheet 8 of 10 Quick Ref Mass Erase Mode Erases All Stages 1 Set Switch S2 position 7 to ON 2 Set jumper ME to ON position centre and bottom pin conn...

Page 9: ...umper to SY on Set jumper MA on Master unit to master position on Set jumper MA on Slave unit to slave position off Position of S2 switch does not affect synch operation 3 Switch on power onto the Mas...

Page 10: ...ne 19 1 4KHz 1 6KHz 1s 1 6KHz 1 4KHz 0 5s NFC48 265 Tone 2 Tone 5 Tone 29 Tone 20 660Hz Continuous Tone 2 Tone 5 Tone 29 Tone 21 554Hz 440Hz 1Hz Alternating Tone 2 Tone 5 Tone 29 Tone 22 544Hz 0 875 s...